| Date |
Text |
| 2002-09-24 00:00:00 | DENIED:MECHANICAL PERMIT 02081954 |
| | |
| | REFERENCE RESPONSE COMMENTS - |
| | 1.DETAIL #9 ON DWG M3.1 - PLEASE NOTE |
| | DETAIL 9 INDICATES A "ROOF EXHAUST |
| | FAN (MUSHROOM TYPE) - CONDENSING |
| | UNIT MINIMUM 18" ABOVE ROOF.THIS |
| | HEIGHT PERTAINS TO UNITS 24"<36". |
| | SEE ATTACHED 2001 FBC TABLE 1511.7. |
| | |
| | REPONSE TO COMMENTS #2 & 3 ARE OKAY. |
| | |
| | 4.PLEASE CLARIFY EQUIPMENT SCHEDULE- |
| | ADDISON HCH094, PROVIDE MANUFACTURER |
| | SUBMITTAL DATA SHOWING THAT THIS |
| | UNIT DOES NOT HAVE THE DESIGN |
| | CAPACITY TO PRODUCE CFM GREATER THAN |
| | 2,000. (ARI MANUAL DOES NOT HAVE A |
| | LISTING FOR ANY ADDISON "HCH" UNITS) |
| | |
| | AS PER 2001 FBC(M) 306.5 ACCESS FOR |
| | EQUIPMENT INSTALLED ON ROOF SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30".PLAN SHEET A-3 ROOF |
| | ACCESS IS ONLY INDICATED ON THE ON SIDE |
| | OF THE PARAPET.PLEASE CLARIFY THE |
| | HEIGHT OF THE PARAPET TO SHOW COMPLAINCE |
| | WITH CODE REQUIREMENT. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |