Date Text
2002-09-24 00:00:00DENIED:MECHANICAL PERMIT 02081954
  
 REFERENCE RESPONSE COMMENTS -
 1.DETAIL #9 ON DWG M3.1 - PLEASE NOTE
 DETAIL 9 INDICATES A "ROOF EXHAUST
 FAN (MUSHROOM TYPE) - CONDENSING
 UNIT MINIMUM 18" ABOVE ROOF.THIS
 HEIGHT PERTAINS TO UNITS 24"<36".
 SEE ATTACHED 2001 FBC TABLE 1511.7.
  
 REPONSE TO COMMENTS #2 & 3 ARE OKAY.
  
 4.PLEASE CLARIFY EQUIPMENT SCHEDULE-
 ADDISON HCH094, PROVIDE MANUFACTURER
 SUBMITTAL DATA SHOWING THAT THIS
 UNIT DOES NOT HAVE THE DESIGN
 CAPACITY TO PRODUCE CFM GREATER THAN
 2,000. (ARI MANUAL DOES NOT HAVE A
 LISTING FOR ANY ADDISON "HCH" UNITS)
  
 AS PER 2001 FBC(M) 306.5 ACCESS FOR
 EQUIPMENT INSTALLED ON ROOF SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30".PLAN SHEET A-3 ROOF
 ACCESS IS ONLY INDICATED ON THE ON SIDE
 OF THE PARAPET.PLEASE CLARIFY THE
 HEIGHT OF THE PARAPET TO SHOW COMPLAINCE
 WITH CODE REQUIREMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.