2002-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHTS P1.0, P2.1, & P4.1 ELECTRIC
 WATER HEATER DETAIL, ROOM #201, & DOMES-
 TIC WATER RISER DIAGRAM, FLOOR DRAIN NOT
 APPROVED FOR INDIRECT WASTE FROM HEATER
 PAN AND RELIEF VALVE DISCHARGE. FLOOR
 SINK IS REQUIRED FOR INDIRECT WASTE.
 SECTION 802.3
 2) SHT P2.1 CONDENSATE SHALL DRAIN SEP-
 ARETLY FROM BLDG. RELIEF VENT REQUIRED
 UPON EXITING BLDG, THEN TIE INTO STORM
 SEWER OR CATCH BASIN. PLEASE PROVIDE
 CONDENSATE RISER DIAGRAM.
 3) SHT P2.2 PLEASE SUBMIT A STORM RISER
 DIAGRAM. SHOW SQ FOOTAGE AS IT ACCUMULA-
 TES IN SYSTEM.
 4) SHT P2.2 PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS.
 5) SHT P4.1 DOMESTIC WATER RISER DIAGRAM
 BACKFLOW REQUIRED. WATER HAMMER ARREST-
 ORS SHALL BE LOCATED NEAR FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT TOP OF DROPS AS
 SHOWN. PDI-WH 201/MANUFACTURE INSTALLAT-
 ION INSTRUCTIONS. SECTION 604.9
  