| Plan Review Notes For Permit 02060115 |
| Permit Number |
02060115 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHTS P1.0, P2.1, & P4.1 ELECTRIC | | | WATER HEATER DETAIL, ROOM #201, & DOMES- | | | TIC WATER RISER DIAGRAM, FLOOR DRAIN NOT | | | APPROVED FOR INDIRECT WASTE FROM HEATER | | | PAN AND RELIEF VALVE DISCHARGE. FLOOR | | | SINK IS REQUIRED FOR INDIRECT WASTE. | | | SECTION 802.3 | | | 2) SHT P2.1 CONDENSATE SHALL DRAIN SEP- | | | ARETLY FROM BLDG. RELIEF VENT REQUIRED | | | UPON EXITING BLDG, THEN TIE INTO STORM | | | SEWER OR CATCH BASIN. PLEASE PROVIDE | | | CONDENSATE RISER DIAGRAM. | | | 3) SHT P2.2 PLEASE SUBMIT A STORM RISER | | | DIAGRAM. SHOW SQ FOOTAGE AS IT ACCUMULA- | | | TES IN SYSTEM. | | | 4) SHT P2.2 PROVIDE CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. | | | 5) SHT P4.1 DOMESTIC WATER RISER DIAGRAM | | | BACKFLOW REQUIRED. WATER HAMMER ARREST- | | | ORS SHALL BE LOCATED NEAR FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT AT TOP OF DROPS AS | | | SHOWN. PDI-WH 201/MANUFACTURE INSTALLAT- | | | ION INSTRUCTIONS. SECTION 604.9 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|