| 2002-07-16 00:00:00 | DENIED: |
| | |
| | 1. NO DETAIL SHOWN ON STANDS FOR ROOF |
| | MOUNTED CONDENSING UNITS. STANDS TO |
| | COMPLY WITH 2001 FBC 1511.7 |
| | |
| | 2. EXHAUST FANS INTERLOCKED WITH AIR |
| | HANDLER UNITS ARE REQUIRED TO RUN AT |
| | ALL TIMES THE BUILDING IS OPERATED IF |
| | FAN IS REQUIRED BY CODE (BATHROOMS ETC.) |
| | |
| | 3. NOTE ON SHEET M5.1 CALLS FOR DUCT |
| | MOUNTED SMOKE DETECTOR PROVIDED BY |
| | SECTION 16 TO BE MOUNTED IN RETURN AIR. |
| | FBC(M) REQUIRES MOUNTING IN SUPPLY AIR. |
| | E2.1 SHOWS SUPPLY AND RETURN DUCT SMOKE |
| | DETECTORS. |
| | |
| | 4. THE ONLY UNIT SHOWN ON THE ELECTRICAL |
| | PLAN AS HAVING DUCT SMOKE DETECTORS IS |
| | AHU1-4. ALL EQUIPMENT WITH A CAPACITY OF |
| | GREATER THAN 2000 CFM REQUIRE DUCT |
| | SMOKE DETECTORS OR SHALL BE INTERLOCKED |
| | TO SHUT OF BY AREA SMOKE DETECTORS IF |
| | INSTALLED IN ACCORDANCE WITH THE FBC. |
| | SEE FBC(M) 606.2.1 |
| | |
| | 5. EQUIPMENT TO BE INSTALLED WITH |
| | RESPECT TO BUILDING CONSTRUCTION TO |
| | ALLOW FOR SERVICE AND REPLACEMENT ON |
| | EQUIPMENT. THIS INCLUDES COIL PULL, |
| | REQUIRED ELECTRICAL ACCESS, AND ACCESS |
| | TO MOTORS AND FANS.FBC(M) 306.1 |