Plan Review Notes
Plan Review Notes For Permit 02060115
Permit Number 02060115
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-07-03 00:00:001) EXIT CORRIDORS ARE NOT THE PROPER
 WIDTH. ALL EXIT CORRIDORS ARE TO BE
 AT LEAST SIX FEET IN WIDTH.
  
 2) DOORS FROM RESTROOMS 202, 204 SWING
 TOO FAR INTO CORRIDOR.
  
 3) PANIC HARDWARE REQUIRED ON ALL
 EXIT DOORS.
  
 4) ADDRESS REQUIRED ON BUILDING.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FOR FIRE ALARM INSTALLATION.
  
 7) PLEASE NOTE PAGE P2.1. IT WAS NOTED
 THAT A FOUR INCH RAIN WATER LITER IS
 PRESENT IN THE STAIRWELL. THIS IS
 NOT PERMITTED.
  
 8) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR EMERGENCY ESCAPE
 WINDOWS.
  
 9) THE AREA DESIGNED ON THE NORTH SIDE
 OF THE BUILDING MUST BE ABLE TO
 SUPPORT FIRE APPARATUS LOADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910