| Plan Review Notes For Permit 02060115 |
| Permit Number |
02060115 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-03 00:00:00 | 1) EXIT CORRIDORS ARE NOT THE PROPER | | | WIDTH. ALL EXIT CORRIDORS ARE TO BE | | | AT LEAST SIX FEET IN WIDTH. | | | | | | 2) DOORS FROM RESTROOMS 202, 204 SWING | | | TOO FAR INTO CORRIDOR. | | | | | | 3) PANIC HARDWARE REQUIRED ON ALL | | | EXIT DOORS. | | | | | | 4) ADDRESS REQUIRED ON BUILDING. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FOR FIRE ALARM INSTALLATION. | | | | | | 7) PLEASE NOTE PAGE P2.1. IT WAS NOTED | | | THAT A FOUR INCH RAIN WATER LITER IS | | | PRESENT IN THE STAIRWELL. THIS IS | | | NOT PERMITTED. | | | | | | 8) PLEASE PROVIDE PRESCRIPTIVE CODE | | | REQUIREMENTS FOR EMERGENCY ESCAPE | | | WINDOWS. | | | | | | 9) THE AREA DESIGNED ON THE NORTH SIDE | | | OF THE BUILDING MUST BE ABLE TO | | | SUPPORT FIRE APPARATUS LOADS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|