| 2002-07-16 00:00:00 | **************** UNSAT ************* |
| | |
| | PLEASE NOTE THAT PLANS ARE MISSING |
| | INFORMATION FOR COMPLETE REVIEW. |
| | |
| | 1)NOTE: PLEASE PROVIDE A LINE DIAGRAM |
| | FOR ELECTRICAL SERVICE. PLEASE INCLUDE |
| | ALL NEW EQUIPMENT, WIRE, CONDUITS, |
| | GROUNDING SYSTEM ETC ETC 215-5 |
| | |
| | 2)NOTE: PLEASE NOTE GROUNDING ELECTRODE |
| | TO INCLUDE FOOTER STEEL/ COLD WATER ETC. |
| | SEE 250-50, SIZING 250-66 |
| | EQUIPMENT GROUNDING CONDUCTORS,250-24, |
| | 250-122. |
| | |
| | 3)NOTE: PLEASE SHOW LOCATIONS OF SERVICE |
| | PLANS SHOW "LP-1" ONLY?? PLEASE NOTE |
| | GROUPING OF MAINS. 230-72 |
| | |
| | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | WITH ALL CONTINUOUS LOADS AND LARGEST |
| | MOTORS AT 125%. 215-3,230-42, 384-16 |
| | ETC. |
| | |
| | 5)NOTE: PLEASE SHOW TRACK LIGHTING CALCS |
| | PER 220-12B |
| | |
| | 6)NOTE: PLEASE NOTE LOAD SHOWN ON E6.2 |
| | EXCEEDS 400A RATING OF MAIN. |
| | |
| | 7)NOTE: PLEASE SEE 700-16 FOR SECOND |
| | MEANS OF ILLUMINATION IN ELEV EQUIPMENT |
| | ROOM. PLEASE CLARIFY IF DUAL BALLAST.? |
| | PLEASE NOTE FIXTURE SCHEDULE ONLYS |
| | MENTIONS 2 LAMPS? |
| | |
| | 8)NOTE: PLEASE NOTE THAT GENERAL NOTES |
| | ON E0.2 MENTION WRONG BLDG CODES/FIRE |
| | CODES. PLEASE CORRECT. PLEASE SEE NEW |
| | FL BLD CODE FOR NEW DATES. |
| | |
| | 9)NOTE: PLEASE NOTE IF ANY NEW DISC`S |
| | ARE ADDED DUE TO GROUPING OF MAINS. |
| | PLEASE SUBMIT AIC RATINGS 110-9 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |