2002-07-16 00:00:00**************** UNSAT *************
  
 PLEASE NOTE THAT PLANS ARE MISSING
 INFORMATION FOR COMPLETE REVIEW.
  
 1)NOTE: PLEASE PROVIDE A LINE DIAGRAM
 FOR ELECTRICAL SERVICE. PLEASE INCLUDE
 ALL NEW EQUIPMENT, WIRE, CONDUITS,
 GROUNDING SYSTEM ETC ETC 215-5
  
 2)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 TO INCLUDE FOOTER STEEL/ COLD WATER ETC.
 SEE 250-50, SIZING 250-66
 EQUIPMENT GROUNDING CONDUCTORS,250-24,
 250-122.
  
 3)NOTE: PLEASE SHOW LOCATIONS OF SERVICE
 PLANS SHOW "LP-1" ONLY?? PLEASE NOTE
 GROUPING OF MAINS. 230-72
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 WITH ALL CONTINUOUS LOADS AND LARGEST
 MOTORS AT 125%. 215-3,230-42, 384-16
 ETC.
  
 5)NOTE: PLEASE SHOW TRACK LIGHTING CALCS
 PER 220-12B
  
 6)NOTE: PLEASE NOTE LOAD SHOWN ON E6.2
 EXCEEDS 400A RATING OF MAIN.
  
 7)NOTE: PLEASE SEE 700-16 FOR SECOND
 MEANS OF ILLUMINATION IN ELEV EQUIPMENT
 ROOM. PLEASE CLARIFY IF DUAL BALLAST.?
 PLEASE NOTE FIXTURE SCHEDULE ONLYS
 MENTIONS 2 LAMPS?
  
 8)NOTE: PLEASE NOTE THAT GENERAL NOTES
 ON E0.2 MENTION WRONG BLDG CODES/FIRE
 CODES. PLEASE CORRECT. PLEASE SEE NEW
 FL BLD CODE FOR NEW DATES.
  
 9)NOTE: PLEASE NOTE IF ANY NEW DISC`S
 ARE ADDED DUE TO GROUPING OF MAINS.
 PLEASE SUBMIT AIC RATINGS 110-9
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  