2002-06-17 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02060176
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 PLAN SHEET MP-2 - AIR HANDLER UNIT
 INSTALLATION DETAIL INDICATES AUXILARY
 DRAIN PAN REQUIRED WITH OVERFLOW
 PROTECTION1997 SMC 304.8.6.1.
 PLEASE NOTE PLAN REVIEW UNDER THE 2001
 FLORIDA BUILDING CODE.
  
 PLAN SHEET MP-2 - AIR CONDITIONING
 SCHEDULE AHU CARRIER 2,000 CFM.ON THE
 PLAN AS WELL AS THE SCHEDULE INDICATES
 A 3.5 TON SYSTEM.ENERGY CALCS ALSO
 CALL FOR A 5 TON SYSTEM.
  
 PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.