| Plan Review Notes For Permit 02060034 |
| Permit Number |
02060034 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-14 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION, MAKE ANY NECESSARY CHANGES | | | ON THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.NO OTHER | | | RECEPTACLES OUTSIDE THE ROOM. | | | | | | 3} PLEASE NOTE THAT AN EQUIPMENT | | | GROUNDING CONDUCTOR IS REQUIRED FROM | | | THE DISCONNECT TO THE PANEL UNLESS THE | | | CONDUIT IS METAL AND BONDED. | | | | | | 4} PLEASE INDICATE THE LOCATION OF THE | | | SERVICE ON THE DRAWING. | | | | | | 5} NOTE THAT A RECEPTACLE IS REQUIRED | | | IN BEDROOM #2 TO COMPLY WITH | | | 210-52(A)(1)(A). | | | | | | 6} PLEASE NOTE THAT ALL KITCHEN | | | COUNTERTOP RECEPTACLES MUST BE | | | GFI'S.(ONE NOT LABLED ) | | | | | | 7} PLEASE CHECK THE CLEARANCE BETWEEN | | | THE PANEL AND THE WATER HEATER TO | | | COMPLY WITH 110-26. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|