| Plan Review Notes For Permit 02051906 |
| Permit Number |
02051906 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) A SERVICE SINK AND DRINKING FOUNTAIN | | | ARE REQUIRED FOR MINIMUM FIXTURE REQUIRE | | | MENT TABLE 403.1 GIVE DETAIL FOR D.F. | | | PER 11-4.24 | | | 2) SHT P-1 KEYNOTES #2 2-1/2" AND SMALL- | | | ER PIPE SHALL HAVE A MINIMUM SLOPE OF | | | 1/4" PER FOOT. TABLE 704.1 | | | 3) SHT A3 URNAL PER 11-4.18 URNAL LIP | | | SHALL BE 1'5" AFF AND HAVE A MINIMUM | | | FLOOR SPACE OF 30"X48". PLEASE SHOW ON | | | PLANS. | | | 4) SHT A3 WATER CLOSETS SHALL BE SET | | | 1'6" TO CENTER OFF WALL. PLEASE SHOW ON | | | PLANS. | | | 5) SHT A3 DETAIL 4 KITCHEN/LOUNGE SINK | | | SHALL COMPLY WITH 11-4.24. EITHER SHOW | | | CLEAR FLOOR SPACE FOR PARALLEL APPROACH | | | OR SHOW DETAIL FOR KNEE CLEARANCE 4.24.3 | | | EXPOSED PIPES 4.24.6 ECT. COUNTER SHALL | | | BE MAX. 2'10" AFF 4.24.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|