| 2002-06-18 00:00:00 | 1) ENTIRE BUILDING IS TO BE COMPLETELY |
| | FIRE SPRINKLER PROTECTED EXCEPT FOR |
| | FPL VAULT. |
| | |
| | 2) WRONG EDITION OF NFPA 13 IS |
| | REFERENCED ON THE PLANS. SHOULD READ |
| | NFPA 13, 1999 EDITION. |
| | |
| | 3) PROPER CLEARANCES OF SEVEN AND HALF |
| | FEET ARE REQUIRED TO THE FRONT AND |
| | SIDES OF ALL FIRE PROTECTION DEVICES. |
| | |
| | 4) THESE PLANS ONLY REFLECT FIRE |
| | SPRINKLER INSTALLATION FOR THE |
| | UNDERGROUND AND FIRST FLOOR ONLY. IT |
| | HAS BEEN EXPLAINED THAT FIRE SPRINKLER |
| | PLANS WILL BE SUBMITTED FOR THE |
| | SECOND FLOOR WHEN MECHANICAL, ELECTRICAL |
| | AND PLUMBING ISSUES HAVE BEEN ADDRESSED. |
| | |
| | 5) ALL SPRINKLER CONTROL VALVES ARE |
| | TO BE SUPERVISED. |
| | |
| | 6) ALL VERTICAL SHAFTS ARE TO BE |
| | PROTECTED WITH FIRE SPRINKLER HEADS. |
| | |
| | 7) ALL FIRE SPRINKLER WORK IS TO BE |
| | DONE IN A QUALITY MANNER AND IS SUBJECT |
| | TO FIELD INSPECTION BY THE FIRE |
| | PREVENTION BUREAU. |
| | |
| | 8) THE FIRE SPRINKLER SYSTEM IS TO |
| | COMPLY WITH NFPA 13, 1999 EDITION. |
| | |
| | 9) THE FIRE PUMP INSTALLATION TO COMPLY |
| | WITH NFPA 20, 2000 EDITION. |
| | |
| | 10) THE STANDPIPE SYSTEM INSTALLATION |
| | TO COMPLY WITH NFPA 14, 2000 EDITION. |
| | |
| | 11) FIRE SPRINKLERS ARE TO BE INSTALLED |
| | UNDER EXTERIOR ROOFS OR CANOPIES |
| | OVER FOUR FEET WIDE. THEY ARE NOT |
| | REQUIRED IF NON COMBUSTIBLE OR |
| | LIMITED COMBUSTIBLE. PLEASE SEE NFPA |
| | 13, 1999 EDITION, SECTION 5-13.8.1. |
| | ANY LOCATION WHERE COMBUSTIBLE MATERIAL |
| | ARE EXPECTED SHALL BE FIRE SPRINKLER |
| | PROTECTED. PLEASE SEE NFPA 13, 1999 |
| | EDITION, SECTION 5-13.8.2. |
| | |
| | 12) VOID SPACES NOTED ON THE PLANS |
| | THAT ARE NON COMBUSTIBLE AND NON |
| | ACCESSIBLE ARE NOTED TO HAVE NO FIRE |
| | SPRINKLERS. PLEASE PROVIDE THIS OFFICE |
| | A LETTER INDICATING THAT NO COMBUSTIBLE |
| | MATERIALS WILL BE LOCATED IN THESE |
| | AREAS. |
| | |
| | 13) SPARE SPRINKLER HEADS, NO LESS THAN |
| | TWENTY FOUR ARE TO BE PROVIDED WITH |
| | A WRENCH.RE: NFPA 13, 1999 EDITION |
| | SECTION 3-2.9.1 |
| | |
| | 14) FIRE SPRINKLER HEADS SUBJECT TO |
| | MECHANICAL DAMAGE ARE REQUIRED TO HAVE |
| | HEAD GUARDS. RE: NFPA 13, 1999 EDITION, |
| | SECTION 3-2.8. |
| | |
| | 15) ANY FIRE SPRINKLERS THAT ARE PAINTED |
| | DURING CONSTRUCTION WILL BE REQUIRED |
| | TO BE REPLACED. RE: NFPA 13, 1999 |
| | EDITION, SECTION 3-2.6.3. |
| | |
| | 16) NO MORE THAN 1000 FIRE SPRINKLERS |
| | SHALL BE LOCATED ON A PRE-ACTION SYSTEM. |
| | RE: NFPA 13, 1999 EDITION, SECTION |
| | 4-3.2.2 AND THE EXCEPTION. |
| | |
| | 17) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | FIRE SPRINKLER HEADS PLANNED FOR USE. |
| | |
| | 18) CORROSION RESISTANT FIRE SPRINKLER |
| | HEADS ARE REQUIRED WHERE MOISTURE |
| | COULD EXIST. RE: NFPA 13, 1999 EDITION, |
| | SECTION 3-2.6.1. |
| | |
| | 19) ALL NEW FIRE SPRINKLER PIPING IS |
| | TO BE PRESSURE TESTED AT 200 PSI FOR |
| | TWO HOURS AND MUST BE WITNESSED BY |
| | FIRE RESCUE PERSONNEL. |
| | |
| | 20) NO BUILDING ARCHITECTURAL OR |
| | STRUCTURAL FEATURES ARE TO INTERFERE |
| | WITH FIRE SPRINKLER HEAD OPERATION. |
| | |
| | APPROVED PROVISO: |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |