2002-06-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE ANY NECESSARY CHANGES IN
 THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE GROUNDS SHOWN ON THE RISER
 DIAGRAM AT PANELS "A","B"AND"C" CREATE
 A PARALLEL PATH TO GROUND WITH THE
 GROUNDED CONDUCTOR FROM MDP,AND MUST BE
 REMOVED PER 250-24(A)(5).
  
 2} THE WASHER(LAUNDRY) CIRCUIT LISTED ON
 PANEL "A" MUST COMPLY WITH 220-16(B).
 (1500 VA).
  
 3} AHU-1,2,& 3 SHOWN IN PANEL "A" MUST
 COMPLY WITH 424-3.(OCP & BC @ 125%)
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE, PER 210-12
  
 6} 2ND FLOOR NORTH STAIRWELL @ LAUNDRY,
 THE SMOKE DETECTOR DOESN'T COMPLY WITH
 2-5.2.1.2(DOOR INTERVENTION) NFPA-72.
  
 7} THE DISCONNECTS SHOWN ST THE ACCU'S
 MUST COMPLY WITH 110-26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  