| Plan Review Notes For Permit 02051878 |
| Permit Number |
02051878 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-17 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE ANY NECESSARY CHANGES IN | | | THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} THE GROUNDS SHOWN ON THE RISER | | | DIAGRAM AT PANELS "A","B"AND"C" CREATE | | | A PARALLEL PATH TO GROUND WITH THE | | | GROUNDED CONDUCTOR FROM MDP,AND MUST BE | | | REMOVED PER 250-24(A)(5). | | | | | | 2} THE WASHER(LAUNDRY) CIRCUIT LISTED ON | | | PANEL "A" MUST COMPLY WITH 220-16(B). | | | (1500 VA). | | | | | | 3} AHU-1,2,& 3 SHOWN IN PANEL "A" MUST | | | COMPLY WITH 424-3.(OCP & BC @ 125%) | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE, PER 210-12 | | | | | | 6} 2ND FLOOR NORTH STAIRWELL @ LAUNDRY, | | | THE SMOKE DETECTOR DOESN'T COMPLY WITH | | | 2-5.2.1.2(DOOR INTERVENTION) NFPA-72. | | | | | | 7} THE DISCONNECTS SHOWN ST THE ACCU'S | | | MUST COMPLY WITH 110-26. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|