2002-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW: PLEASE SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES.
 TO THE BEST OF MY CALCULATIONS THE MIN-
 IMUM FACILITIES ARE NOT BEING MET.
 MALE WATER CLOSETS REQUIRED - 3
 FEMALE WATER CLOSETS REQUIRED - 6
 MALE LAVS REQUIRED - 2
 FEMALE LAVS REQUIRED - 2 TABLE 403.1
 2) PLEASE PROVIDE MEASURMENTS FOR ALL
 TOILET ROOMS.
 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES. INDICATE 5' TURNING RADIUS FOR
 EACH TOILET ROOM.
 4) DOOR SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF ANY HDCP FIXTURE. SEC.
 11-4.22.2
 5) IF TOILET STALLS ARE PROVIDED, THEN
 AT LEAST ONE SHALL BE A STANDARD TOILET
 STALL COMPLYING WITH 11-4.17 WITH THE
 SIZE AND ARRANGEMENT ACCORDING TO 11-4.
 17.3. SEC 11-4.22.4
 6) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM. SHOW ALL PIPE SIZES.
 7) PLEASE PROVIDE A WATER RISER DIAGRAM
 SHOW PIPE SIZES AND PROVIDE WATER HAMMER
 ARRESTORS PER SEC 604.9 LOCATE WATER
 HAMMERS NEAR FIXTURE IN AN "EFFECTIVE
 RANGE" NOT AT TOP OF DROP.
  