| 2002-08-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) FROM PREVIOUS REVIEW: PLEASE SUBMIT | | | CALCULATIONS FOR MINIMUM FACILITIES. | | | TO THE BEST OF MY CALCULATIONS THE MIN- | | | IMUM FACILITIES ARE NOT BEING MET. | | | MALE WATER CLOSETS REQUIRED - 3 | | | FEMALE WATER CLOSETS REQUIRED - 6 | | | MALE LAVS REQUIRED - 2 | | | FEMALE LAVS REQUIRED - 2 TABLE 403.1 | | | 2) PLEASE PROVIDE MEASURMENTS FOR ALL | | | TOILET ROOMS. | | | 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP | | | FIXTURES. INDICATE 5' TURNING RADIUS FOR | | | EACH TOILET ROOM. | | | 4) DOOR SHALL NOT SWING INTO THE CLEAR | | | FLOOR SPACE OF ANY HDCP FIXTURE. SEC. | | | 11-4.22.2 | | | 5) IF TOILET STALLS ARE PROVIDED, THEN | | | AT LEAST ONE SHALL BE A STANDARD TOILET | | | STALL COMPLYING WITH 11-4.17 WITH THE | | | SIZE AND ARRANGEMENT ACCORDING TO 11-4. | | | 17.3. SEC 11-4.22.4 | | | 6) PLEASE PROVIDE A SANITARY RISER DIA- | | | GRAM. SHOW ALL PIPE SIZES. | | | 7) PLEASE PROVIDE A WATER RISER DIAGRAM | | | SHOW PIPE SIZES AND PROVIDE WATER HAMMER | | | ARRESTORS PER SEC 604.9 LOCATE WATER | | | HAMMERS NEAR FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT AT TOP OF DROP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|