| 2002-06-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) TO DETERMINE MINIMUM FACILITIES REQD |
| | IN TABLE 403.1 (PLUMBING) MORE INFORMAT- |
| | ION IS REQUIRED. TABLE 1003.1 (BLDG), |
| | ASSEMBLY - IS SEATING TO BE FIXED? PRO- |
| | VIDE INFORMATION FOR EACH HALL. - PLEASE |
| | SUBMIT CALCULATIONS FOR MINIMUM FACILIT- |
| | IES. |
| | 2) SHT A-2 ROOF PLAN, PLEAS SUBMIT CAL- |
| | CULATIONS FOR PRIMARY AND SECONDARY ROOF |
| | DRAINS PER SECTIONS 1106 & 1107. ADD 1/2 |
| | AREA OF ALL VERTICAL WALLS. SHOW LOCAT- |
| | IONS OF ALL DRAINS. TO VERIFY ADEQUATE |
| | DRAINAGE FOR BLDG. |
| | 3) SHTS D-1/D-2 SEPARATE GAS PERMIT RE- |
| | QUIRED FOR GAS DEMO. NOTE #6 |
| | 4) SHT D-1 NOTES #7, 10, & 11 - ALL |
| | PLUMBING CAPPED OFF SHALL BE INSPECTED |
| | BEFORE COVERING. |
| | 5) SHT D-1 NOTE #12 REMOVE GAS W/HEATER |
| | (SAVE FOR RE-USE) AND SHT D-2 NOTE #17 |
| | VIRIFY THAT GAS METER IS OFF, VERIFY IF |
| | GAS COMPANY WILL REMOVE?? WILL THERE BE |
| | A GAS W/HEATER IN BLDG,?? PLEASE CLAIRFY |
| | 6) SHT E-1 ONE SHOWER IN MEN'S AND WO- |
| | MEN'S SHOWER ROOMS SHALL COMPLY WITH |
| | 11-4.21. PLEASE PROVIDE DETAIL SHOWING |
| | COMPLIANCE WITH SEC'S 4.21.2, 4.21.3, |
| | 4.21.4, 4.21.5, 4.21.6, & 4.21.7. |
| | 6) A SERVICE SINK IS REQUIRED PER TABLE |
| | 403.1 |
| | |