2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) TO DETERMINE MINIMUM FACILITIES REQD
 IN TABLE 403.1 (PLUMBING) MORE INFORMAT-
 ION IS REQUIRED. TABLE 1003.1 (BLDG),
 ASSEMBLY - IS SEATING TO BE FIXED? PRO-
 VIDE INFORMATION FOR EACH HALL. - PLEASE
 SUBMIT CALCULATIONS FOR MINIMUM FACILIT-
 IES.
 2) SHT A-2 ROOF PLAN, PLEAS SUBMIT CAL-
 CULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107. ADD 1/2
 AREA OF ALL VERTICAL WALLS. SHOW LOCAT-
 IONS OF ALL DRAINS. TO VERIFY ADEQUATE
 DRAINAGE FOR BLDG.
 3) SHTS D-1/D-2 SEPARATE GAS PERMIT RE-
 QUIRED FOR GAS DEMO. NOTE #6
 4) SHT D-1 NOTES #7, 10, & 11 - ALL
 PLUMBING CAPPED OFF SHALL BE INSPECTED
 BEFORE COVERING.
 5) SHT D-1 NOTE #12 REMOVE GAS W/HEATER
 (SAVE FOR RE-USE) AND SHT D-2 NOTE #17
 VIRIFY THAT GAS METER IS OFF, VERIFY IF
 GAS COMPANY WILL REMOVE?? WILL THERE BE
 A GAS W/HEATER IN BLDG,?? PLEASE CLAIRFY
 6) SHT E-1 ONE SHOWER IN MEN'S AND WO-
 MEN'S SHOWER ROOMS SHALL COMPLY WITH
 11-4.21. PLEASE PROVIDE DETAIL SHOWING
 COMPLIANCE WITH SEC'S 4.21.2, 4.21.3,
 4.21.4, 4.21.5, 4.21.6, & 4.21.7.
 6) A SERVICE SINK IS REQUIRED PER TABLE
 403.1
  
 REVIEW BY KEN STEVENS