| Plan Review Notes For Permit 02051873 |
| Permit Number |
02051873 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-23 00:00:00 | DENIED: | | | | | | INSUFFICIENT INFORMATION FOR REVIEW | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | 2.PLEASE CLARIFY VENTILATION FOR | | | UTILITY RM.WILL THIS SPACE BE USED | | | FOR STORAGE? | | | | | | 3.VERIFY EXHAUST AND MAKE-UP AIR FOR | | | THE EXISTING BATHROOM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|