Plan Review Notes
Plan Review Notes For Permit 02051873
Permit Number 02051873
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-06-07 00:00:001) CHANGE OF USE. ASSEMBLY OCCUPANCY
 FROM A MERCANTILE OCCUPANCY.
  
 2) BUILDING IS LOCATED IN FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY. PLEASE
 SEE LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE, SECTION F.
  
 3) PLANS DO NOT INDICATE OCCUPANT
 LOADS, FURNITURE, OR SEATING
 ARRANGEMENTS.
  
 4) PLEASE EXPLAIN EXIT SIGN LEADING
 PERSONS INTO PROP STORAGE AREA.
  
 5) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS.
  
 6) PLANS MAKE REFERENCE TO VARIOUS
 LOCKING DEVICES ON DOORS. IF OCCUPANT
 LOADS ARE GREATER THAN 100 PERSONS,
 PANIC HARDWARE IS REQUIRED. LOCKS ON
 EXIT DOORS IF LESS THAN 100 PERSONS,
 SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, SPECIAL KNOWLEDGE OF EFFORT.
  
 7) MORE INFORMATION IS REQUIRED ON THE
 PLATFORM. IS IT TEMPORARY OR PERMANANT.
 ANY STAIRS OR RAMPS PROVIDED FOR THE
 PLATFORM.
  
 8) ANY PORTABLE FIRE EXTINGUISHERS
 PROVIDED.
  
 9) BUILDING ADDRESS REQUIRED ON STREET
 ELEVATION SIDE.
  
 10) WHAT IS THE STATUS OF THE EXISTING
 FIRE SPRINKLER SYSTEM BELIEVED TO
 BE PRESENT INSIDE THE BUILDING.
  
 11) DUCT SMOKE DETECTORS REQUIRED IN
 AIR HANDLING DEVICES OVER 2000 CFM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910