| 2002-06-07 00:00:00 | 1) CHANGE OF USE. ASSEMBLY OCCUPANCY |
| | FROM A MERCANTILE OCCUPANCY. |
| | |
| | 2) BUILDING IS LOCATED IN FIRE LIMITS. |
| | CERTAIN RESTRICTIONS APPLY. PLEASE |
| | SEE LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, SECTION F. |
| | |
| | 3) PLANS DO NOT INDICATE OCCUPANT |
| | LOADS, FURNITURE, OR SEATING |
| | ARRANGEMENTS. |
| | |
| | 4) PLEASE EXPLAIN EXIT SIGN LEADING |
| | PERSONS INTO PROP STORAGE AREA. |
| | |
| | 5) NO INTERIOR FINISH CLASSIFICATION |
| | INFORMATION FOR WALLS AND CEILINGS. |
| | |
| | 6) PLANS MAKE REFERENCE TO VARIOUS |
| | LOCKING DEVICES ON DOORS. IF OCCUPANT |
| | LOADS ARE GREATER THAN 100 PERSONS, |
| | PANIC HARDWARE IS REQUIRED. LOCKS ON |
| | EXIT DOORS IF LESS THAN 100 PERSONS, |
| | SHALL NOT REQUIRE THE USE OF A KEY, |
| | TOOL, SPECIAL KNOWLEDGE OF EFFORT. |
| | |
| | 7) MORE INFORMATION IS REQUIRED ON THE |
| | PLATFORM. IS IT TEMPORARY OR PERMANANT. |
| | ANY STAIRS OR RAMPS PROVIDED FOR THE |
| | PLATFORM. |
| | |
| | 8) ANY PORTABLE FIRE EXTINGUISHERS |
| | PROVIDED. |
| | |
| | 9) BUILDING ADDRESS REQUIRED ON STREET |
| | ELEVATION SIDE. |
| | |
| | 10) WHAT IS THE STATUS OF THE EXISTING |
| | FIRE SPRINKLER SYSTEM BELIEVED TO |
| | BE PRESENT INSIDE THE BUILDING. |
| | |
| | 11) DUCT SMOKE DETECTORS REQUIRED IN |
| | AIR HANDLING DEVICES OVER 2000 CFM. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |