Plan Review Notes
Plan Review Notes For Permit 02051873
Permit Number 02051873
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-06 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE NOTE NO INFORMATION
 SUBMITTED FOR EXISTING PANEL(S) SIZE ETC
 PLEASE SUBMIT LOAD CALCULATIONS FOR NEW
 LOADS AND SHOW ALL CONTINUOUS LOADS
 AT 125%.215-5/220-3/220-10,11,13 ETC.
  
 2)NOTE: PLEASE NOTE NEW WATER HEATER
 SHOWN AS NEW RECEPT. PLEASE NOTE WH IS
 REQD TO BE HARDWIRE WITH A MEANS OF
 DISCONNECT. PLEASE SHOW.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SHOW WINDOW OUTLETS> 210-62
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGNAGE CIRCUIT?600-5
  
 5)NOTE: PLEASE NOTE CIRCUITS NEED TO BE
 SHOWN ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 6)NOTE: PLEASE CLARIFY IF "ALL" RECEPTS
 SHOWN ARE EXISTING AS NOTED ON NOTE "N"?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DWEEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372