| 2002-06-06 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE NO INFORMATION | | | SUBMITTED FOR EXISTING PANEL(S) SIZE ETC | | | PLEASE SUBMIT LOAD CALCULATIONS FOR NEW | | | LOADS AND SHOW ALL CONTINUOUS LOADS | | | AT 125%.215-5/220-3/220-10,11,13 ETC. | | | | | | 2)NOTE: PLEASE NOTE NEW WATER HEATER | | | SHOWN AS NEW RECEPT. PLEASE NOTE WH IS | | | REQD TO BE HARDWIRE WITH A MEANS OF | | | DISCONNECT. PLEASE SHOW. | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SHOW WINDOW OUTLETS> 210-62 | | | | | | 4)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGNAGE CIRCUIT?600-5 | | | | | | 5)NOTE: PLEASE NOTE CIRCUITS NEED TO BE | | | SHOWN ON PLANS AND CORRELATE WITH A | | | SUBMITTED PANEL SCHEDULE. | | | | | | 6)NOTE: PLEASE CLARIFY IF "ALL" RECEPTS | | | SHOWN ARE EXISTING AS NOTED ON NOTE "N"? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DWEEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|