| Date |
Text |
| 2002-06-12 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02051873 |
| | ADD: 421 IRIS ST |
| | CONT: PRESIDENTIAL CONST |
| | TEL: 622-7057 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE 2 CURRENT COPIES OF SIGNED & |
| | SEALED SURVEYS WITH PROPOSED IMPROVEMENT |
| | TO BE COMPLETED. |
| | |
| | 2) THE FIRE MARSHALL INDICATES A CHANGE |
| | IN USE, FROM MERCANTILE TO ASSEMBLY. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH CO.,THE PERMIT PLANS STAMPED BY |
| | THEM AND THE RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. CHANGE OF USE |
| | REQUIRES COUNTY ASSESSMENT. |
| | |
| | 4) WHAT TYPE CONSTRUCTION IS THIS BUILD? |
| | DOES THIS BUILDING CONTAIN A ACTIVE |
| | FIRE SPRINKLER? |
| | |
| | 5) NOTE: DEPENDING ON THE ADDITIONAL |
| | INFORMATION THIS MAY APPLY, THIS BUILD- |
| | ING IS LOCATED IN A "FIRE DISTRICT" SEE |
| | CITY AMENDMENTS FOR FIRE DISTRICT OF |
| | 2001 FL BLD CODE. |
| | |
| | 6) ADDITIONAL INFORMATION REQUIRED: |
| | HALL ONE INDICATES SOME TYPE OF STRUC- |
| | TURE THERE IS NO NOTE AS TO WHAT IT IS? |
| | OR WHAT IT IS MADE OF? |
| | |
| | 7) PLEASE PROVIDE A SEATING PLAN FOR THE |
| | DIFFERENT HALLS, INDICATE LIFE SAFETY |
| | EXITING WITH COMMON PATH OF TRAVEL |
| | 1019.1.3. WILL SEATING BE FIXED SEATING? |
| | |
| | 8) MIXED OCCUPANCY, SEE TABLE 704.1: |
| | ASSEMBLY 2HRS. / STORAGE S1 2HR VS. |
| | STORAGE S2 3 HRS. PLEASE INDICATE RATED |
| | WALLS. |
| | |
| | 9) 1012.4 DURING ITS SWING, ANY DOOR IN |
| | A MEANS OF EGRESS SHALL LEAVE UNOBSTRUCT |
| | ED AT LEAST 1/2 OF THE REQUIRED WIDTH OF |
| | AN AISLE, CORRIDOR, PASSAGEWAY, OR LAND- |
| | ING NOR PROJECT MORE THAN 7" INTO THE |
| | REQUIRED MEANS OF EGRESS. SEE DOORS IN |
| | CORRIDOR 1&2. |
| | |
| | 10) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 11)TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 12) SHEET E-1 INDICATES EXIT SIGNS ON |
| | BOTH SIDES OF THE DOORS THAT LEAD INTO |
| | THE PROP ROOM? |
| | |
| | 13) FL ACCESSIBILITY PLANS INDICATE |
| | RAMPS AT THE ENTRANCE DOORS THE SLOPE |
| | IA NOT GIVEN NOR EITHER IS THERE A LAND- |
| | ING AT THE TOP OR BOTTOM. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |