Plan Review Notes
Plan Review Notes For Permit 02051849
Permit Number 02051849
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-03 00:00:00 
 1. PLAN SHEET M2.1 NOTE #4, COORDINATE
 EXACT LOCATION OF "CHASE".PLEASE
 INDICATE IF "CHASE" IS A FIRE RATED
 CHASE.
  
 2. DUCT SMOKE DETECTORS REQUIRED AS PER
 2001 FBC(M) 606.2.2.
  
 3. CLARIFY REFRIGERANT LINES OVER STAIRS
 IS THIS A STAIRWELL?
  
 4. INDICATE THE RATING OF THE CEILING IN
 THE CORRIDOR.
  
 5. PLAN SHEET M0.1 DETAIL 1, INDICATES
 REFRIGERANT LINES "ENCLAPSULATED"
 WITH 4" RIGID PIPE. AS PER 2001 FBC,
 MECHANICAL 1107.6, PIPE JOINTS SHALL
 BE EXPOSED FOR VISUAL INSPECTION
 PRIOR TO BEING COVERED OR ENCLOSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.