| Notes |
| Date |
Text |
| 2002-06-11 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE OUTSIDE ARE CALCUALTIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | PROVIDE MANUFACTURER INSTALLATION DATA | | | FOR THE CONDENSER UNIT STANDS OR | | | ENGINEERED DETAIL. | | | | | | WHERE EQUIPMENT & APPLIANCES REQUIRING | | | ACCESS ARE INSTALLED ON ROOFS AT A | | | HEIGHT EXCEEDING 16 FT SHALL HAVE A | | | PERMANENT MEANS OF ACCESS.2001 FBC(M) | | | 306.5. | | | | | | INDICATE ALL NEW OR EXISTING FIRE | | | DAMPERS ON PLAN AS PER 2001 FBC(M) | | | 607.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|