| 2003-05-23 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | AND RESUBMIT FOR REVIEW. | | | | | | 1} THE CIRCUIT #'S FOR THE HAND DRYERS 9 | | | & 17 ON THE SCHEDULE DON'T CORRELATE | | | WITH THE CIRCUIT NUMBERS ON THE PLAN. | | | | | | 2} PLEASE PROVIDE COMPLETED LOAD CALC'S | | | WITH TOTALS GIVEN. | | | | | | 3} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATEDAND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|