Plan Review Notes
Plan Review Notes For Permit 02051827
Permit Number 02051827
Review Stop E
Sequence Number 4
Notes
Date Text
2003-04-28 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE INFORMATION ON
 RISER/PANEL SCHEDULES AS TO NEW FEED
 FOR LIFT STATION CONTROLLER RACK.?
 PLEASE REVISE LOAD CALCUALTIONS FOR
 ABOVE. PLEASE SHOW ALL CONTINOUS AND
 MOTOR LOADS AT 125%. 215-3/230-42
 PLEASE SHOW LOAD CALCS. 220-3,220-10,
 220-11,220-13 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE ALSO NOTE, PER FS ALL PLANS/
 SHEETS SUBMITTED FOR RECORD MUST BE
 SIGNED, DATED AND SEALED BY THE ARCH
 OF RECORD. 481.221
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 OWES REV FEE.