| Notes |
| Date |
Text |
| 2002-09-23 00:00:00 | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW. | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | 2.PLEASE PROVIDE EQUIPMENT INFORMATION | | | IN ACCORDANCE WITH ENERGY CACLS. | | | | | | 3.PROVIDE DUCT MATERIAL, SIZE AND | | | LAYOUT. | | | | | | 4.INDICATE CONDENSATE LINE SIZE, | | | PIPING MATERIAL AND TERMINATION | | | POINT. | | | | | | PLEASE PROVIDE THE ABOVE INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|