Plan Review Notes
Plan Review Notes For Permit 02051827
Permit Number 02051827
Review Stop M
Sequence Number 2
Notes
Date Text
2002-09-23 00:00:00INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 2.PLEASE PROVIDE EQUIPMENT INFORMATION
 IN ACCORDANCE WITH ENERGY CACLS.
  
 3.PROVIDE DUCT MATERIAL, SIZE AND
 LAYOUT.
  
 4.INDICATE CONDENSATE LINE SIZE,
 PIPING MATERIAL AND TERMINATION
 POINT.
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.