Plan Review Notes
Plan Review Notes For Permit 02051827
Permit Number 02051827
Review Stop P
Sequence Number 1
Notes
Date Text
2002-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL
 HEALTH. 901 EVERNIA STREET WPB 33401
 (561) 355-3018 PRIOR TO RESUBMITTING FOR
 PLAN REVIEW.
 2) SHT A3 DETAILS 5/A-3 & 7/A-3 HDCP
 TOILET SHALL BE 17" TO 19" HEIGH SECTION
 11-4.16.3 AND TOILET SHALL BE 18" FROM
 CENTER TO WALL. FIG 28.
 3) SHT A6 PLUMBING NOTES #13 - AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 4) SHT A6 FLOOR SINKS ARE REQUIRED FOR
 ALL INDIRECT WASTE. THE FOLLOWING FIX-
 TURES REQUIRE INDIRECT WASTE, 3-COMP
 SINK, ICE MACHINE, & ALL SODA W/ICE BINS
 PLEASE SHOW FLOOR SINKS FOR THESE FIXS.
 5) SHT A6 GREASE TRAP NOT APPROVED IN
 CONCESSION STAND. PLEASE CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE MANAGER
 FOR SIZE AND LOCATION OF GREASE TRAP.
 (561) 837-4074.
 6) SHT A6 IF GREASE TRAP REQUIRED, THE
 GREASE LINE WILL BE RUN SEPARATE FROM
 THE SANITARY LINE.
 7) SHT A6 SANITARY RISER DIAGRAM AND
 WATER RISER DIAGRAM, PLEASE SHOW ALL
 PIPE SIZES FOR DRAINAGE, VENT, AND WATER
 LINES. WATER HAMMER ARRESTORS ARE REQUI-
 RED FOR QUICK CLOSING VALVES PER SEC
 604.9
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377