| 2002-06-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) ROUTE PLANS TO THE PALM BEACH COUNTY |
| | HEALTH UNIT, DIVISION OF ENVIRONMENTAL |
| | HEALTH. 901 EVERNIA STREET WPB 33401 |
| | (561) 355-3018 PRIOR TO RESUBMITTING FOR |
| | PLAN REVIEW. |
| | 2) SHT A3 DETAILS 5/A-3 & 7/A-3 HDCP |
| | TOILET SHALL BE 17" TO 19" HEIGH SECTION |
| | 11-4.16.3 AND TOILET SHALL BE 18" FROM |
| | CENTER TO WALL. FIG 28. |
| | 3) SHT A6 PLUMBING NOTES #13 - AIR |
| | CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | 4) SHT A6 FLOOR SINKS ARE REQUIRED FOR |
| | ALL INDIRECT WASTE. THE FOLLOWING FIX- |
| | TURES REQUIRE INDIRECT WASTE, 3-COMP |
| | SINK, ICE MACHINE, & ALL SODA W/ICE BINS |
| | PLEASE SHOW FLOOR SINKS FOR THESE FIXS. |
| | 5) SHT A6 GREASE TRAP NOT APPROVED IN |
| | CONCESSION STAND. PLEASE CONTACT RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE MANAGER |
| | FOR SIZE AND LOCATION OF GREASE TRAP. |
| | (561) 837-4074. |
| | 6) SHT A6 IF GREASE TRAP REQUIRED, THE |
| | GREASE LINE WILL BE RUN SEPARATE FROM |
| | THE SANITARY LINE. |
| | 7) SHT A6 SANITARY RISER DIAGRAM AND |
| | WATER RISER DIAGRAM, PLEASE SHOW ALL |
| | PIPE SIZES FOR DRAINAGE, VENT, AND WATER |
| | LINES. WATER HAMMER ARRESTORS ARE REQUI- |
| | RED FOR QUICK CLOSING VALVES PER SEC |
| | 604.9 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |