2007-07-31 13:50:51TRUSS DRAWING PACKAGE CHECKLIST:
 1- AS REQUESTED ON PREVIOUS CHECKLIST DATED 7-6-07THE
 TRUSSES NEED TO INCLUDE THE ATTIC LIVE LOAD AS REQUIRED
 BY TABLE 1604.1 FBC 2001.
 ENGINEER RESPONDED WITH LETTER SAYING THAT THIS IS A
 NON CONCURRENT LOAD. THIS IS NOT CORRECT.
 ENGINEER TO READ SECTION 1604.1 OF FBC 2001. THIS TRUSS
 PACKAGE DOESN'T MEET THE MINIMUM CODE REQUIREMENTS.
 (NOTE: THIS IS NOT ONLY REQUIRED BY THE FLORIDA
 BUILDING CODE,BUT BY THE ASCE 7-98 STANDARD ALSO. SEE
 SEC. 4.2.1).
  
 2- EACH INDIVIDUAL SHEET SHALL HAVE ENGINEER'S ORIGINAL
 SIGNATURE, NOT COPY OF SIGNATURE AS REQUIRED BY CHAPTER
 471 FLORIDASTATUTE.
  
 3- PRODUCT APPROVAL PACKAGE SUBMITTED IS OK.
  