Plan Review Notes
Plan Review Notes For Permit 02051793
Permit Number 02051793
Review Stop E
Sequence Number 3
Notes
Date Text
2007-05-01 16:34:18PANEL SCHEDULES "A" & 'B"HAVE NOT BEEN ADJUSTED FOR
 ALL NEW LOADS.
  
 PANELS 'A' , 'B' LOAD CALCULATIONS HAVE NOT BEEN
 ADJUSTED FOR NEW LOADS
  
 SEE PLAN WITH GREEN HIGHLIGHTER FOR NEW LOADS THAT ARE
 SHOWN ON THIS DRAWINGS.
  
 FIELD INSPECTOR STATES THAT ALL TUBS ARE NOW SPAS AND
 THIS IS NOT SHOWN ON DRAWINGS.
  
 SPAS THAT ARE SHOWN ON SECOND FLOOR THE LARGE ONE SHOW
 TWO (2) SWITCHES WITHIN 5' OF SPA
 SEE SECTION 680.43 (C) FOR VIOLATION.
  
 IF THE OTHER TUBS ARE SPAS YOU WILL HAVE THE SAME
 VIOLATION ON THE ONES ON THE SECOND AND FIRST FLOORS
 WHERE THE SWITCHES ARE WITHIN 5' OF THE SPA.
  
 PANEL "B" SHOWS ON RISER AS A 24 CIRCUIT PANEL AND IT
 IS A 42 CIRCUIT PANEL.