| Notes |
| Date |
Text |
| 2007-05-01 16:34:18 | PANEL SCHEDULES "A" & 'B"HAVE NOT BEEN ADJUSTED FOR | | | ALL NEW LOADS. | | | | | | PANELS 'A' , 'B' LOAD CALCULATIONS HAVE NOT BEEN | | | ADJUSTED FOR NEW LOADS | | | | | | SEE PLAN WITH GREEN HIGHLIGHTER FOR NEW LOADS THAT ARE | | | SHOWN ON THIS DRAWINGS. | | | | | | FIELD INSPECTOR STATES THAT ALL TUBS ARE NOW SPAS AND | | | THIS IS NOT SHOWN ON DRAWINGS. | | | | | | SPAS THAT ARE SHOWN ON SECOND FLOOR THE LARGE ONE SHOW | | | TWO (2) SWITCHES WITHIN 5' OF SPA | | | SEE SECTION 680.43 (C) FOR VIOLATION. | | | | | | IF THE OTHER TUBS ARE SPAS YOU WILL HAVE THE SAME | | | VIOLATION ON THE ONES ON THE SECOND AND FIRST FLOORS | | | WHERE THE SWITCHES ARE WITHIN 5' OF THE SPA. | | | | | | PANEL "B" SHOWS ON RISER AS A 24 CIRCUIT PANEL AND IT | | | IS A 42 CIRCUIT PANEL. |
|