Plan Review Notes
Plan Review Notes For Permit 02051793
Permit Number 02051793
Review Stop R
Sequence Number 2
Notes
Date Text
2002-10-08 00:00:00CHECKLIST:
 1-SURVEY AND PLANS DON'T MATCH. SURVEY
 SHOWS OLD HOUSE. NOT THE NEW LAYOUT.
 2-PROVIDE RECEIPT OF PAID IMPACT FEES.
 3-NOTICE OF COMMENCEMENT WASN'T RECORDED
 IN THE COURTHOUSE.
 4-WINDOW SCHEDULE IS NOT CLEAR. EXTERIOR
 ELEVATIONS SHOW SINGLE HUNG WINDOWS.
 PRODUCT APPROVAL SUBMITTED IS FOR
 CASEMENT WINDOWS. ALSO, CLARIFY SIZES
 CALLED ON WINDOW SCHEDULE. EG: WHAT IS
 A PELLA #322020? ETC.
 5-SOIL TEST REPORT TO HAVE ORIGINAL SEAL
 AND SIGNATURE AS REQ'D BY CHAPTER 471
 FL. STATUTES WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
 6-THERE WASN'T PRODUCT APPROVAL & STRUC-
 TURAL SPECS SUBMITTED FOR THE EPICORE
 FLOOR SYSTEM TO BE USED. SEC 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-ARCHITECT TO PROVIDE REVIEW STAMP AT
 ANY PRODUCT APPROVAL OR SHOP DRAWING.
 THIS SHOW PROOF OF REVIEW DONE BY HIM.
 8-ITEM #14 FROM PREVIOUS CHECKLIST IS
 STILL UNCLEAR.SOME STRUCTURAL WALL
 SECTIONS SHOW MONOLITHIC CONCRETE SLAB
 AND OTHERS SHOW CONCRETE SLAB WITH
 EXPANSION JOINT. CLARIFY WHY?.
 RESPONSE TO ITEM #14 CALLS FOR ALL CON
 CRETE WORK TO BE MONOLITHIC. SEE STRUC
 TURAL WALL SECTIONS AND CLARIFY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9-WHERE IS THE BEAM SCHEDULE? SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)SKYLIGHT.
 B)INSWING FRENCH DOORS AS SHOWN ON PLANS
 C)INSWING FRENCH DOORS WITH TRANSOM
 ABOVE SINGLE ASSEMBLY AS SHOWN ON PLAN
 D)FIXED WINDOWS. SEE SIZES ON PLANS BY
 STAIRWAY AND AT MASTER BATHROOM.
 E)ROOF TILE.
 F)FLAT ROOF SYSTEM.
 G)FIREPLACE UL LISTING AND SPECS.
 H)BBQ UL LISTING AND SPECS.
 11-SPECIFY HOW TO GET THE R-11 INSUL. AT
 MASONRY WALLS AS SPECIFIED ON THE
 ENERGY CALCS.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 12-PROVIDE FRAMING DETAILS FOR SKYLIGHT.
 BUILDING SECTION ON SHEET A-10 DOESN'T
 HAVE ENOUGH STRUCTURAL INFORMATION.
 SPECIFY ALL FASTENERS. ETC.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-CLARIFY IF USING STORM SHUTTERS OR
 MISSILE IMPACT GLASS GLAZING. PRODUCT
 APPROVAL SUBMITTED IS FOR MISSILE
 IMPACT GLAZING. IF USING STORM SHUTTER
 THEN PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. ALSO, SPECIFY
 ON PRODUCT APPROVAL DWGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHORS TYPE &
 SPACING TO BE USED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001 & CITY STANDARD
 FOR STORM SHUTTERS INSTALLATION.
 14-OWES $793.83 FOR UPDATED VALUE AND
 RADON FEES.
 15-PROVIDE SHORING PLANS AND SPECIFICA-
 TIONS FOR INSTALLATION OF CONCRETE
 FLOOR SYSTEM AS CALLED FOR EPICORE
 SYSTEM. SEC. 104.2.1.2 CITY AMENDMENTS