| 2002-06-26 00:00:00 | DENIED:MECHANICAL PERMIT 02061129 |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | 2001 FBC(M) 402.2 - NATURAL VENTILATION |
| | FOR OUTSIDE AIR REQUIRMENT. SHOW |
| | COMPLIANCE FOR THE MINIMUM OPENABLE AREA |
| | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR |
| | AREA BEING VENTILATED) OR TABLE 403.3 |
| | FOR MECHANICAL VENTILATION. |
| | |
| | SMOKE DETECTORS SHALL BE INSTALLED |
| | SUPPLY SYSTEMS WITH A DESIGN CAPACITY |
| | GREATER THAN 2,000 CFM, IN THE SUPPLY |
| | AIR DUCT. 2001 FBC(M) 606.2.1OR |
| | UPON ACTIVATION, THE SMOKE DETECTORS |
| | SHALL SHUTDOWN THE AIR DISTRIBUTION |
| | SYSTEM. 2001 FBC(M) 606.4 |
| | |
| | PLEASE NOTE PLAN SHEET M-1 THE TWO DROPS |
| | LOCATED IN THE KITCHEN AREA, FLEX SIZE |
| | IS NOT INDICATED ON PLAN. |
| | |
| | OVERFLOW PROTECTION REQUIRED AS PER |
| | 2001 FBC(M) 307.2.3. |
| | |
| | SHOULD A GAS DRYER BE INSTALLED - |
| | SHOW COMPLIANCE FOR COMBUSTION AIR AS |
| | PER 2001 FBC(M) CHAPTER 7. |
| | |
| | PLEASE NOTE, EXHAUST AIR SHALL NOT BE |
| | DIRECTED ONTO WALKWAYS AS PER 2001 FBC |
| | (M) 401.5.2. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |