Plan Review Notes
Plan Review Notes For Permit 02051793
Permit Number 02051793
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SHOW PANEL"B" LOCATION ON THE
 DRAWING.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} PLEASE NOTE THAT IN B-108,ANOTHER
 GFI IS REQUIRED PER 210-52(D).(DOUBLE
 SINK IS SHOWN ON E-1.)
  
 5} SMOKE DETECTORS ARE REQUIRED IN AND
 OUT OF BEDROOMS PER 2-2.1.1.1 NFPA-72.
  
 6} PLEASE ADD RECEPTACLES TO MEET THE
 REQUIREMENT OF 210-52(A)(1),NOTE THE
 STEREO ROOM.
  