| Notes |
| Date |
Text |
| 2002-05-31 00:00:00 | UNSAT | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE REFER TO FS/FAC 553.79(6)(A) AND | | | RESUBMIT UNDER SAME. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR AT | | | THE 600 AMP DISCONNECT IS INCORRECT FOR | | | PARALLEL 350 MCM. PLEASE REFER TO TABLE | | | 250-66. | | | | | | 2} THERE SHOULD NOT BE A NEUTRAL TO THE | | | PRIMARY OF THE TRANSFORMER. | | | | | | 3} PLEASE INDICATE WHERE THE GEC IS | | | LOCATED FOR THE SEPERATELY DERIVED | | | SYSTEM PER 250-30. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|