| 2003-03-28 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 10/1/02: |
| | |
| | 10) FBC* 104.2.1.2THE SUBMITTED |
| | STRUCTURAL SHEETS AU1 TO AU13 DO NOT |
| | INCLUDE A DETAIL FOR WALL PANEL |
| | ANCHORAGE TO THE FOUNDATIONS.SUBMIT A |
| | TYPICAL DETAIL TO SHOW HOW THE S5 WALL |
| | PANEL JOISTS ARE ANCHORED TO THE |
| | FOUNDATIONS. |
| | |
| | 12) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS. |
| | |
| | 13) WINDOW PRODUCT APPROVALS.SUBMIT |
| | PRODUCT APPROVALS FOR THE FIXED WINDOWS, |
| | AND THE ARCHED LITE WINDOWS ABOVE THE |
| | DOORS AND CASEMENT WINDOWS.ALSO, THE |
| | SUBMITTED CASEMENT WINDOW PRODUCT |
| | APPROVAL NOA# 02-1224.10 IS MISSING |
| | DRAWING SHEET 1 OF 2.SHEET 2 OF 2 |
| | CANNOT BE READ DUE TO POOR COPY QUALITY. |
| | SUBMIT LEGIBLE AND COMPLETE COPIES OF |
| | THE REQUIRED PRODUCT APPROVALS. |
| | |
| | 14) WINDOW MULLIONS AND TRANSOMS. |
| | DRAWING SHEETS 1 TO 3 OF 3 OF THE |
| | SUBMITTED TRACO MULLION PRODUCT APPROVAL |
| | NOA# 01-1218.01 CANNOT BE READ DUE TO |
| | POOR COPY QUALITY.SUBMIT LEGIBLE |
| | COPIES. |
| | |
| | 15) INSWING AND OUTSWING DOUBLE ENTRANCE |
| | DOORS.SHEETS 1,3,4 & 5 OF THE |
| | SUBMITTED PRODUCT APPROVAL |
| | NOA# 01-0314.23 AND NOA# 01-0314.21 |
| | STATE THAT THAT THE MAXIMUM ALLOWABLE |
| | OPENING HEIGHT IS 80 11/16".THIS IS |
| | SIGNIFICANTLY LESS THAN THE 8'-0" HEIGHT |
| | SPECIFIED IN THE DOOR SCHEDULE ON |
| | DRAWING SHEET A-4.SUBMIT PRODUCT |
| | APPROVALS WHICH ARE APPROPRIATE FOR THE |
| | SPECIFIED DOOR OPENING SIZES. |
| | |
| | 16) FRENCH DOORS.THE SUBMITTED PRODUCT |
| | APPROVAL NOA# 99-0909.02 IS MISSING |
| | DRAWING SHEETS 3 THRU 9 OF 9.ALSO, THE |
| | SUBMITTED COPIES OF THE DRAWING SHEETS |
| | ARE POOR QUALITY.SUBMIT LEGIBLE COPIES |
| | |
| | 17) GARAGE DOOR.THE DRAWING SHEETS FOR |
| | THE SUBMITTED STEEL GARAGE DOOR PRODUCT |
| | APPROVAL NOA# 00-1212.03 CANNOT BE READ |
| | PROPERLY DUE TO POOR COPY QUALITY.THIS |
| | PRODUCT APPROVAL IS FOR A 16' WIDE DOOR |
| | AND IS NOT APPLICABLE FOR THE 18' WIDE |
| | GARAGE DOOR SPECIFIED ON THE PLANS. |
| | SUBMIT AN APPROPRIATE AND LEGIBLE |
| | PRODUCT APPROVAL. |
| | |
| | 18) HURRICANE MISSILE IMPACT PROTECTION |
| | SHUTTERS.THE NEWLY SUBMITTED |
| | SOUTHEASTERN METALS STORM PANEL SHUTTER |
| | PRODUCT APPROVAL NOA# 02-0809.02 IS |
| | MISSING DRAWING SHEET 1 OF 2.SHEET 2 |
| | OF 2 CANNOT BE READ DUE TO POOR COPY |
| | QUALITY.SUBMIT LEGIBLE AND COMPLETE |
| | COPIES OF THE PRODUCT APPROVALS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |