| 2002-10-01 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SITE PLAN.ONE OF THE SUBMITTED |
| | COPIES OF SHEET SP-1 IS AN OLD REVISION |
| | (SIGNED AND SEALED ON 12/8/01) AND DOES |
| | NOT PROVIDE SUFFICIENT INFORMATION.THE |
| | OTHER SUBMITTED COPY (SIGNED AND SEALED |
| | ON 2/15/02) IS ACCEPTABLE.A SECOND |
| | COPY OF THE REVISED SHEET SP-1 IS |
| | REQUIRED. |
| | |
| | 4) SHEET SP-1, SITE PLAN. GENERAL NOTE 1 |
| | SHALL NOT REFER TO THE STANDARD BUILDING |
| | CODE AS IT IS NOT CURRENT.AMEND NOTE 1 |
| | TO REFER TO THE FLORIDA BUILDING CODE |
| | 2001. |
| | |
| | 5) FBC 1804SUBMIT A FOUNDATION PLAN |
| | SHOWING THE FOOTINGS, PAD BASES, SLAB |
| | THICKNESS, AND COLUMN AND BEARING WALL |
| | LOCATIONS. |
| | |
| | 6) FBC 1804.2.2SOIL REPORT.THE FIRST |
| | 2(?) SHEETS OF THE ARDAMAN & ASSOCIATES |
| | SOIL REPORT ARE MISSING FROM THE |
| | COPIES.THE FIRST SHEET OF THE DOCUMENT |
| | AS SUBMITTED IS ENTITLED 'SUBSURFACE |
| | EXPLORATION INFORMATION', SUBMIT TWO |
| | COPIES OF THE SHEETS THAT SHOULD PRECEED |
| | THIS. |
| | |
| | 7) FBC* 104.2.1.2SUBMIT A ROOF PLAN, |
| | WHICH SHOULD INCLUDE ROOF SHEATHING NAIL |
| | SPACING DETAILS AND A ROOF TRUSS ANCHOR |
| | SCHEDULE. |
| | |
| | 8) FBC 1606.1.7WIND LOADS.THE PLANS |
| | SHALL STATE THE FOLLOWING INFORMATION |
| | USED IN THE DESIGN:BASIC WIND SPEED, |
| | WIND IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| | AND DESIGN WIND PRESSURES FOR THE DESIGN |
| | OF EXTERIOR COMPONENT AND CLADDING |
| | MATERIALS. |
| | |
| | 9) ROOF TILES.THE ELEVATIONS SHOW CLAY |
| | BARREL ROOF TILES, BUT TYPICAL WALL |
| | SECTION 3/SP-1 AND THE SUBMITTED PRODUCT |
| | APPROVAL REFER TO CEMENT/CONCRETE S-TILE |
| | AMEND THE PLANS OR SUBMIT AN ALTERNATIVE |
| | PRODUCT APPROVAL SUCH THAT THE DOCUMENTS |
| | CORRELATE. |
| | |
| | 10) FBC* 104.2.1.2SUBMIT DETAILS OF |
| | THE PRECAST CONCRETE PANEL SYSTEM TO BE |
| | USED FOR THE EXTERIOR WALLS.THESE |
| | SHALL INCLUDE DETAILS OF SHEAR WALLS TO |
| | TRANSFER THE WIND LOADS TO THE FOOTINGS. |
| | |
| | 11) FBC 2405.2THE FRENCH DOOR/SIDELITE |
| | GLAZING IS IN A 'HAZARDOUS LOCATION' AND |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 12) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 13) WINDOW PRODUCT APPROVAL.THE ONLY |
| | SUBMITTED WINDOW PRODUCT APPROVAL |
| | NOA# 02-0612.04 IS FOR SINGLE HUNG |
| | WINDOWS.THIS WINDOW TYPE DOES NOT |
| | CORRELATE TO THE WINDOW SCHEDULE ON |
| | SHEET A-4, WHICH SPECIFIES CASEMENT |
| | WINDOWS AND FIXED WINDOWS.SUBMIT |
| | PRODUCT APPROVALS WHICH CORRELATE TO THE |
| | SPECIFIED WINDOW TYPES. |
| | |
| | 14) WINDOW MULLIONS AND TRANSOMS. |
| | SUBMIT PRODUCT APPROVALS FOR THE |
| | MULLIONS AND TRANSOMS AS MAY BE REQUIRED |
| | BY THE WINDOW PRODUCT APPROVAL (SEE |
| | COMMENT 13 ABOVE) FOR MULLED WINDOW UNIT |
| | APPLICATIONS. |
| | |
| | 15) INSWING DOUBLE ENTRANCE DOORS. |
| | DRAWING SHEETS 1,3,4 & 5 OF THE |
| | SUBMITTED PRODUCT APPROVAL |
| | NOA# 01-0314.23 STATE THAT THE MAXIMUM |
| | OPENING HEIGHT IS 80 11/16".THIS IS |
| | SIGNIFICANTLY LESS THAN THE 8'-0" HEIGHT |
| | SPECIFIED IN THE DOOR SCHEDULE ON |
| | DRAWING SHEET A-4.SUBMIT A PRODUCT |
| | APPROVAL WHICH IS APPROPRIATE FOR THE |
| | SPECIFIED DOOR OPENING SIZE. |
| | |
| | 16) FRENCH DOORS.THE SUBMITTED PRODUCT |
| | APPROVAL NOA# 99-0902.02 IS MISSING |
| | DRAWING SHEETS 3 THRU 9 OF 9.ALSO, THE |
| | SUBMITTED COPIES OF THE DRAWING SHEETS |
| | ARE POOR QUALITY.SUBMIT LEGIBLE COPIES |
| | |
| | 17) SHEET A-3, GARAGE BUCK DETAIL 5/A-4. |
| | THE VALIDITY OF THIS DETAIL CANNOT BE |
| | VERIFIED AS THE DRAWING SHEETS FOR THE |
| | SUBMITTED STEEL GARAGE DOOR PRODUCT |
| | APPROVAL NOA# 00-1212.03 ARE VERY POOR |
| | QUALITY COPIES AND CANNOT BE READ. |
| | SUBMIT LEGIBLE COPIES. |
| | |
| | 18) HURRICANE MISSILE IMPACT PROTECTION |
| | SHUTTERS.DRAWING SHEET 2 OF THE |
| | SUBMITTED GALVANIZED STEEL STORM PANEL |
| | SHUTTER PRODUCT APPROVAL NOA# 99-0318.03 |
| | STATES THAT THE MAXIMUM PANEL LENGTH IS |
| | 86".THESE PANELS WILL NOT BE LONG |
| | ENOUGH TO COVER THE STRUCTURAL OPENING |
| | REQUIRED FOR THE LIVING ROOM FRENCH |
| | DOOR #9 AND THE CABANA FRENCH DOOR #2 |
| | AND THEIR ASSOCIATED SIDE LITES.SUBMIT |
| | AN APPROPRIATE PRODUCT APPROVAL FOR |
| | THESE DOORS. |
| | |
| | 19) INFORMATIVE: |
| | SHEET A-1.SECTION MARKERS C/A-3 AND |
| | B/A-3 SHOULD BE SWAPPED SO THAT THEY |
| | CORRESPOND WITH THE CROSS-SECTIONS |
| | SHOWN ON SHEET A-3. |
| | |
| | 20) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |