| Plan Review Notes For Permit 02051645 |
| Permit Number |
02051645 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-06 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE SOIL TEST REPORT SIGNED AND | | | SEALED BY THE ENGINEER. | | | 2-STORM SHUTTERS: | | | A)DRAWINGS DON'T MATCH PRODUCT APPROVAL. | | | B)DRAWINGS ARE NOT LEGIBLE. | | | C)VERIFY IF OPENINGS ARE THE SAME AS | | | SHOWN ON THE SUBMITTED PLANS. | | | 3-PROVIDE PRODUCT APPROVAL FOR: | | | A)ENTRY DOORS PRODUCT APPROVAL & DWGS | | | ARE NOT LEGIBLE (NOTE: BE AWARE THAT | | | THIS PRODUCT WILL EXPIRE 8-31-02. KEEP | | | IN MIND FOR FUTURE SUBMITTALS. | | | B)SINGLE HUNG WINDOWS PRODUCT APPROVAL | | | REPORT FIRST PAGE DOESN'T MATCH THE | | | REST OF THE REPORT AND DRAWINGS. | | | RESUB. CORRECT REPORT AND DRAWINGS. | | | 4-SPECIFY FIREBLOCKING MATERIAL AND | | | LOCATION AT STAIRS (MISSING SIZE AND | | | THER IS NOT FIREBLOCKING SHOWN ON TOP | | | OF STAIRS. SEE SEC. 2305.1.4 FBC 2001. |
|