| 2002-06-21 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-DIRECT ENTRY FROM GARAGE TO BONUS BED- |
| | ROOM IS NOT ALLOWED BY SEC. 411.2.8 |
| | FBC 2001. |
| | 3-24SH WINDOW SIZE TYP. DON'T PROVIDE |
| | THE MIN 24" CLEAR HEIGHT & 5.7 S.F. |
| | CLEAR OPENING REQ'D BY SEC. 1005.4.4 |
| | FBC 2001. IS THIS CUSTOM MADE WINDOW? |
| | 4-REVISE A/C AREA IN ENERGY CALCULATIONS |
| | TO MATCH ARCHITECTURAL PLANS. |
| | 5-SPECIFY FIRECUTS AT MASONRY WALL AS |
| | REQ'D BY SEC. 2305.4 FBC 2001. |
| | 6-PROVIDE SPECS TO PROTECT SOIL & FOOT'G |
| | FROM WATER FALLING FROM ROOF VALLEYS. |
| | SEC. 1804.1.6 FBC 2001. |
| | 7-PROVIDE SOIL TEST REPORT. |
| | 8-PROVIDE DESIGN OF JOINTS @ CONC. SLAB. |
| | SEC. 1909.3 FBC 2001 (OR SPECIFY WWM |
| | SUPPORTS. SEE EXCEPTION ON SEC. 1909.3 |
| | 9-STORM SHUTTERS: |
| | A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AND KEY PLAN. SEE ATTACHED CITY SAMPLE |
| | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS & ANCHOR TYPE AND |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO. |
| | 10-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS AS SHOWN ON PLANS. |
| | B)COMPLETE DADE COUNTY PRODUCT APPROVAL |
| | FOR "PAN AMERICAN" WINDOW MULLIONS |
| | SINCE WINDOWS ARE FROM PAN AMERICAN. |
| | 11-PROVIDE UPDATED ORIGINAL LETTER FOR |
| | MASONRY TO BE USED. LETTER ADDRESSED |
| | TO CITY OF WPB. IDENTIFY PROJECT AND |
| | CONTRACTOR. |
| | 12-SPECIFY FIREBLOCKING MATERIAL AND |
| | LOCATION AT STAIRS. SEC. 2305.1.4 FBC. |
| | 13-SPECIFY DRAFSTOPPING MATERIAL AND |
| | LOCATION @ 2ND FL FRAMING PLAN AS |
| | REQ'D BY SEC. 2305.2.2 FBC 2001. |