| 2002-08-12 00:00:00 | CHECKLIST: |
| | 1-PROVIDE ENGINEERING ANALYSIS & CALCS. |
| | CLARIFY HOW ARE WIND WINDLOADS BEING |
| | CONTINUOUSLY TRANSFERED TO THE FLOOR |
| | & CEILING DIAPHRAGMS. SEE SECTIONS |
| | 1606.2.4, 2105 AND 2107 FBC 2001. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-SEE COMMENTS ON PLANS. PLEASE RETURN |
| | REVIEWED SET AFTER CORRECTIONS ARE |
| | DONE TO EXPEDITE REVIEW PROCESS. |
| | 4-SPECIFY FIRE CUTS ON STRUCTURAL DETAIL |
| | SECTIONS ALSO. SEC. 2105.1.4 FBC 2001. |
| | 5-PROVIDE SOIL TEST REPORT. |
| | 6-PROVIDE COMPLETE INFORMATION FOR STORM |
| | SHUTTERS. KEY PLAN AND COMPLETE INSTA- |
| | LLATION SCHEDULE. PRODUCT APPROVAL W/ |
| | MATCHING LEGIBLE DRAWINGS. |
| | 7-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOOR WITH LEGIBLE DRAWINGS. |
| | B)ARCHED WINDOWS WITH DWGS THAT MATCH |
| | THE PRODUCT APPROVAL. |
| | C)GLASS BLOCK COMPLETE UL SPECIFICATIONS |
| | FOR ONE HR FIRE RATED ASSEMBLY. |
| | 8-REVISE DETAIL FOR 2X STRUCTURAL BUCK |
| | REQUIRED BY THE PRODUCT APPROVAL. SEE |
| | DETAIL SUBMITTED AND DETAIL FOR FRAM'G |
| | AT ARCHED OPENINGS. THEY DON'T MATCH. |
| | 9-SPECIFY FIREBLOCKING SIZE AND LOCATION |
| | AT STAIRS, INCLUDING AT TOP OF STAIRS. |
| | SEC. 2105.1.4 FBC 2001. |
| | 10-REVISE CONNECTORS SPECIFIED AT TOP |
| | OF FRAMING WALLS. NEED WOOD TO WOOD |
| | CONNECTOR. CONNECTOR SPECIFIED IS TO |
| | BE EMBEDED IN CONCRETE. |
| | 11-PROVIDE COMPLETE DETAILS AND SPECS |
| | FOR CONSTRUCTION AND INSTALLATION OF |
| | WOOD FRAMED SHEAR WALL. SEE SECTION |
| | 2313 FBC 2001. |