| 2002-06-20 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-REVISE SIZE OF ATTIC ACCESS. NOTE #14. |
| | 36" MIN.(NOT 30"). SEC. 2309.6 FBC. |
| | 3-CLARIFY SIZE OF EGRESS WINDOWS. 24SH & |
| | 34SH DON'T PROVIDE 24" MIN. CLEAR HT. |
| | ALSO, 24SH DON'T PROVIDE THE 5.7 S.F. |
| | MIN. CLEAR OPENING. SEC 1005.4.4 FBC |
| | 4-SEE COMMENTS ON PLANS. PLEASE RETURN |
| | REVIEWED SET TO EXPEDITE REVIEW. |
| | 5-SPECIFY FIRECUTS AT MASONRY WALL AS |
| | REQUIRED BY SEC. 2305.4 FBC 2001. |
| | 6-PROVIDE SPECIFICATIONS FOR SOIL AND |
| | FOOTING PROTECTION WHEN IMPACTED BY |
| | WATER FROM VALLEYS. SEC. 1804.1.6 FBC. |
| | 7-PROVIDE SOIL TEST REPORT. |
| | 8-DESIGN JOINTS AT CONCRETE SLAB. SEC. |
| | 1909.3 FBC. (OR SPECIFY WWM SUPPORTS. |
| | SEE SEC. 1909.3 FBC 2001). |
| | 9-STORM SHUTTERS: |
| | A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AND KEY PLAN. |
| | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS & ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO. |
| | 10-PROVIDE PRODUCT APPROVAL FOR: |
| | A)SINGLE ENTRY DOOR AS SHOWN ON PLANS. |
| | B)COMPLETE DADE COUNTY PRODUCT APPROVAL |
| | FOR PAN AMERICAN WINDOW MULLIONS SINCE |
| | WINDOWS USED ARE PANAMERICAN NO LAWSON |
| | C)ARCHED WINDOWS NEED LEGIBLE DRAWINGS. |
| | 11-PROVIDE UPDATE ORIGINAL LETTER OF |
| | MASONRY TO BE USED. LETTER TO BE |
| | ADDRESSED TO CITY OF WPB CLEARLY |
| | IDENTIFYING PROJECT AND CONTRACTOR. |
| | 12-PROVIDE 2X STRUCTURAL BUCK DETAIL AS |
| | REQ'D BY PRODUCT APPROVAL SUBMITTED |
| | FOR ARCHED WINDOWS. |
| | 13-AREA CALCULATIONS DON'T MATCH. SEE |
| | SHEET C-1 AND A-1. REVISE AS REQUIRED. |
| | 14-BRING BACK DWGS TO PALM BEACH COUNTY |
| | TO HAVE A/C AREAS REVISED AS REQUIRED. |
| | 15-NEED A COMPLETE BATHRM @ 1ST FL. WITH |
| | DOOR WITH 29" MIN. CLEAR OPEN'G. |
| | MASTER BATHRM WATER CL. DOOR DOESN'T |
| | PROVIDE IT. (NOTE: POWDER RM DOESN'T |
| | COUNT AS BATHRM) SEC 11-11 FBC 2001. |
| | 16-PROVIDE COMPLETE DETAILS & UL SPECS |
| | FOR 1HR FIRE RATED GLASS BLOCK |
| | ASSEMBLY AT ZERO LOT LINE WALL. AS |
| | REQ'D BY TABLE 600 FBC 2001. |
| | 17-TRUSS ANCHOR SCHEDULE & ROOF FRAMING |
| | PLAN DON'T MATCH REVISE & CLARIFY. |
| | 18-WHERE IS THE ROOF SHEATHING NAILING |
| | SCHEDULE? NO SHOWN ON PLANS. |
| | 19-GABLE END DETAIL IS MISSING SOME |
| | CONNECTORS. ALSO, VERIFY THAT GABLE |
| | END IS STRUCTURAL CONTINUOUS AS REQ'D |
| | BY SECTION 2313.4 FBC 2001. |
| | 20-REVISE ENERGY CALCULATIONS TO MATCH |
| | A/C AREAS THAT MATCH THIS HOUSE. SEE |
| | SHEET A-1. |