| Plan Review Notes For Permit 02051561 |
| Permit Number |
02051561 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) WHERE ARE THE TOILET FACILITIES FOR | | | PERSONS WORKING IN THE GARAGE? | | | 2) WHAT IS THE REASON FOR THE SHOWERS? | | | OUTSIDE SHOWERS ARE NOT ALLOWED TO DRAIN | | | INTO THE SANITARY SYSTEM. | | | 3) PLEASE INDICATE WHAT TYPE OF WORK | | | WILL BE DONE IN THE GARAGE. (SHT A2.0 | | | SHOWS WORK BENCHES) | | | 4) PLEASE INDICATE THE NATURE OF MATER- | | | IALS BEING STORED. | | | 5) DEPENDING ON INFORMATION RECIEVED, AN | | | OIL OR OIL/SAND INTERCEPTOR MIGHT BE RE- | | | QUIRED. IF SO IT SHALL BE SIZED BY | | | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE | | | MANAGER, (561) 837-4074 | | | 6) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|