| Plan Review Notes For Permit 02051528 |
| Permit Number |
02051528 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-19 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) PROVIDE (2) COPIES OF UPDATED SOIL | | | REPORTS WHICH REFERENCE THE 2001 FLORIDA | | | BUILDING CODE. | | | | | | 2) THE WELDED WIRE MESH IN THE CONCRETE | | | PAD IS REQUIRED TO BE SUPPORTED PER FBC | | | SEC. 1909.3. | | | | | | 3) THE WINDOW IN BATHROOM #2 WHICH IS | | | WITHIN 3 FEET OF THE TUB IS REQUIRED TO | | | BE SAFETY GLAZING PER FBC SEC. 2405.2(2) | | | | | | 4) THE GLASS BLOCK IN AT THE MASTER BATH | | | TUB IS REQUIRED TO HAVE A MINIMUM | | | UNIFORM FACE THICKNESS OF .25". | | | | | | NOTE: PLEASE INDICATE THE ABOVE | | | INFORMATION ON THE PLANS FOR FUTURE | | | SUBMITTALS. | | | | | | 5)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - WINDOWS (#2 & #4) ARCHED TOP FIXED | | | GLASS WINDOWS | | | - GLASS BLOCK | | | | | | NOTE: TRUSS DRAWINGS ARE NO LONGER | | | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW | | | THEY WILL BE REQUIRED TO BE ON THE JOB | | | SITE AT TRUSS INSPECTION. A SIGNED AND | | | SEALED SET FOR PUBLIC RECORD IS REQUIRED |
|