| Plan Review Notes For Permit 02051499 |
| Permit Number |
02051499 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-08-16 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | DUE TO THE EXPECTED WIND PRESSURES, THE | | | 3'X5' WINDOWS IN ZONE 5 (DEFINED AS PER | | | FBC FIGURE 1606.2(C)) SHALL NOT | | | INCORPORATE GLASS TYPE '2' AS PER | | | PRODUCT APPROVAL NOA# 01-1002.03. | | | | | | --PROVISO-- | | | SUBMIT BETTER COPIES OF THE WINDOW | | | MULLION PRODUCT APPROVAL NOA# 02-0123.07 | | | ENSURING THAT THE ANCHOR LOAD CHARTS ARE | | | ARE LEGIBLE. |
|