| Plan Review Notes For Permit 02051499 |
| Permit Number |
02051499 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-01 00:00:00 | DENIED: | | | | | | PLANS INDICATE DUCTWORK RUNNING THROUGH | | | THE STAIRWELL.AS PER 2001 FBC | | | 1006.1.3.1, PENETRATIONS INTO AND | | | OPENINGS THROUGH A STAIRWAY ENCLOSURE | | | ASSEMBLY ARE PROHIBITED EXECPT FOR | | | DUCTOWRK & EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|