| 2002-08-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 6/14/02: |
| | |
| | 1) RESPONSE NOTED.A RECORDED COPY OF |
| | THE NOTICE OF COMMENCEMENT WILL BE |
| | SUBMITTED BEFORE PERMIT ISSUE. |
| | |
| | 2) FBC 1606.1.4WINDOW AND EXTERIOR |
| | DOORS: |
| | -THE SUBMITTED DOOR PRODUCT APPROVAL |
| | NO. 02-0129.01 STATES THAT THE PROPOSED |
| | DOOR HAS NO MISSILE IMPACT RATING. |
| | SPECIFY HURRICANE MISSILE IMPACT |
| | PROTECTION SHUTTERS OR PROVIDE A PRODUCT |
| | APPROVAL FOR AN APPROPRIATE IMPACT |
| | RESISTANT DOOR. |
| | -STATE THE POSITIVE AND NEGATIVE |
| | DESIGN WIND PRESSURES TO DETERMINE THE |
| | APPLICABILITY OF THE SUBMITTED WINDOW |
| | PRODUCT APPROVAL (NOA NO. 01-1002.03) |
| | FOR THE REQUIRED WINDOW SIZES AND IMPACT |
| | RESISTANCE.ALSO, A NUMBER OF THE EAST |
| | ELEVATION WINDOWS REQUIRE MULLIONS, AND |
| | DRAWING SHEET 1, OF THE SUBMITTED WINDOW |
| | PRODUCT APPROVAL, REFERS TO A SEPARATE |
| | CGI MULLION NOA FOR MULLION/MULTIPLE |
| | UNITS.SUBMIT A COMPLETE PRODUCT |
| | APPROVAL. |
| | |
| | 3) FIRST FLOOR PLAN AE101, REFERS TO |
| | STAIRWAY DETAIL 10/AE501.SHEET AE501 |
| | HAS NO DETAIL 10 BUT THERE ARE TWO |
| | DETAIL 8'S.AMEND SHEET AE101 AND/OR |
| | AE501 FOR EASE OF INTERPRETATION IN THE |
| | FIELD. |
| | |
| | 9) FBC 11-4.19.3DETAIL 1/AE401.THE |
| | AMENDMENT TO THE CHASE, FOR CLEARANCE IN |
| | FRONT OF THE MEN'S ACCESSIBLE LAVATORY |
| | IS NOTED, HOWEVER THE 48" MIN. DEPTH OF |
| | CLEAR SPACE IS MEASURED FROM THE CENTER- |
| | LINE OF THE DRAIN OUTLET, NOT FROM THE |
| | REAR WALL (REF. FIG. 32). |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |