| Date |
Text |
| 2002-06-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHTS AE101, AE102, AE103 & AE401, |
| | PER 11-4.17 ACCESSIBLE W/C SHALL BE |
| | LOCATED IN THE CORNER, DIAGONAL TO THE |
| | DOOR. |
| | 2) SHTS AE103 & AE401, TOILET ROOM #312 |
| | SHALL BE ACCESSIBLE PER 11-4.1.3(11) AND |
| | 11-4.1.6(1)(B) |
| | 3) SHT AE401 PLEASE SHOW CLEAR FLOOR |
| | SPACE FOR ALL HDCP FIXTURES, AND 5 FOOT |
| | TURNING RADIUS IN ALL TOILET ROOMS. (NOT |
| | REQUIRED IN STALLS) |
| | 4) SHTS AE101, AE102, AE103 & AE401, |
| | DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OF ANY FIXTURE. 11-4.17.5, |
| | 11-4.22.2, & 11-4.23.2 TURNING RADIUS |
| | SHALL BE UNOBSTRUCTED AND DOORS SHALL |
| | NOT OPEN INTO THEM. |
| | 5) SHTS P1.1, P1.2, P1.3, STALLS IN ROOM |
| | 115B, 215B, 314B, & SANT RISER DIAGRAM. |
| | FLOOR DRAINS IN THESE ROOMS ARE NOT |
| | VENTED. |
| | 6) SHT P2.1 WATER HEATER DETAIL. PER |
| | 504.7.1 THE DISCHARGE PIPE FROM THE T/P |
| | RELIEF LINE SHALL NOT HAVE ANY TRAPPED |
| | SECTIONS AND SHALL HAVE A VISIBLE AIR |
| | GA[ OR AIR GAP FITTING LOCATED IN THE |
| | SAME ROOM AS THE WATER HEATER. |
| | 7) PLEASE SUBMIT MANUFACTURE INFORMATION |
| | FOR INSTANTANIOUS WATER HEATER. SHOWING |
| | LISTING FROM APPROVED TESTING AGENCY. |
| | 8) SERVICE SINKS ARE REQUIRED FOR EACH |
| | FLOOR SO EACH TENANT SPACE SHALL COMPLY |
| | WITH TABLE 403.1 FBC |
| | 9) SHT AE401, DETAIL E, ELEC. WATER |
| | COOLER. PROVISIONS SHALL BE MADE FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. (HI/LOW OR DRINKING CUP DISP- |
| | ENSER) |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |