| Plan Review Notes For Permit 02051499 |
| Permit Number |
02051499 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-11 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89. | | | | | | PLEASE INDICATE ON PLAN ALL FIRE DAMPERS | | | AS PER2001 FBC(M) 607.6.1. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|