| 2002-06-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC 1606.1.4SHEET AE201, ELEVATIONS |
| | SUBMIT PRODUCT APPROVALS FOR THE NEW |
| | WINDOWS AND EXTERNAL DOORS. |
| | |
| | 3) FBC 1007.3SHEET AE101, NOTE 5. |
| | SUBMIT DETAILS TO SHOW THE RISER HEIGHT |
| | AND TREAD DEPTH FOR THE RECONFIGURED |
| | STAIRWAY AT LANDING 105. |
| | |
| | 4) FBC 705.1.2.1FIRE RATING OF DOORS. |
| | DOORS 124, 207, 218, AND 308 SHALL HAVE |
| | A FIRE RESISTANCE OF ONE-HOUR (REF. FBC |
| | TABLE 705.1.2).DOORS 107, 118, 205, |
| | 302 AND 318 WHICH ARE SHOWN ON THE DOOR |
| | SCHEDULE AS HAVING A FIRE RESISTANCE OF |
| | 45 MINUTES SHOULD ALSO BE ONE-HOUR. |
| | |
| | 5) FBC 705.1.2.1FIRE RESISTANCE OF |
| | INTERIOR WALLS AT OPENINGS.SHEET GI001 |
| | PROJECT INFORMATION PROPOSES A 20 MINUTE |
| | FIRE-RATING FOR ACCESS OPENINGS IN SHAFT |
| | ENCLOSURES.TABLE 705.1.2 REQUIRES |
| | OPENING PROTECTIVES WITH A FIRE |
| | RESISTANCE OF ONE-HOUR.AMEND SHEET |
| | GI001 TO DEMONSTRATE COMPLIANCE. |
| | |
| | 6) FBC 11-4.19.2DETAIL D/AE401. |
| | LAVATORY LEG CLEARANCE.THE DIMENSION |
| | SHOWN AS 27" MAX. FROM THE FLOOR TO THE |
| | UNDERSIDE OF THE LAVATORY SHOULD BE |
| | 27" MIN. (REF. FIG. 31).AMEND SHEET |
| | AE401. |
| | |
| | 7) FBC 11-4.16.4DETAIL A/AE401. GRAB |
| | BAR POSITIONING.THE DIMENSION SHOWN AS |
| | 12" MAX. BETWEEN THE 42" LONG GRAB BAR |
| | AND THE W.C. WALL SHOULD BE FIXED AT 12" |
| | (NOT MAX.) SUCH THAT THE OTHER END OF |
| | THE GRAB BAR WILL BE NO LESS THAN 54" |
| | FROM THE W.C. WALL (REF. FIG. 29(B)). |
| | AMEND SHEET AE401. |
| | |
| | 8) FBC 11-4.16.2DETAIL 1/AE401.THE |
| | CENTER-LINE OF THE WOMEN'S ACCESSIBLE |
| | W.C. SHOULD BE 1'6" FROM THE SIDE WALL |
| | (REF. FIG. 28) |
| | |
| | 9) FBC 11-4.19.3DETAIL 1/AE401.THE |
| | CLEAR FLOOR SPACE IN FRONT OF THE MEN'S |
| | ACCESSIBLE LAVATORY SHOULD COMPLY WITH |
| | THE REQUIREMENTS SHOWN IN FIG. 32.THE |
| | PROXIMITY OF THE LAVATORY TO THE SIDE |
| | WALL PROJECTION ('CHASE') COMPROMISES |
| | THE ARRANGEMENT. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |