| Plan Review Notes For Permit 02051353 |
| Permit Number |
02051353 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-05 00:00:00 | PLUMBING PLAN DENIED, PES FBC-G 2001 | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER STANDARD | | | GAS CODE. | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE STANDARD GAS CODE SECS. 305.2 THRU | | | 305.4 AND TABLES 305.4(A) THRU 305.4(E). | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | THE STANDARD GAS CODE SEC. 305.4(I). | | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X 8233 |
|