2002-06-19 00:00:00PROVISO:MECHANICAL PERMIT 02051349
  
 REFERENCE LAUNDRY ROOM - MAKEUP AIR
  
 PLEASE INDICATE ON PLAN COMPLIANCE WITH
 2001 FBC(M) CHAPTER 7, COMBUSTION AIR.
 1. PROVIDE MANUFACTURER SUBMITTAL OF THE
 GAS DRYER TO BE INSTALLED AND
 2. SHOW COMPLIANCE WITH 2001 FBC(M)
 703.2 #2 (A) & (B) OR
 3. PROVIDE LOUVERED DOOR
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  