| Plan Review Notes For Permit 02051346 |
| Permit Number |
02051346 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-10 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS PER 210-12 | | | | | | 2)NOTE: PLEASE NOTE MISSING GFI FOR | | | COND UNITS. | | | | | | 3)NOTE: PLEASE CLARIFY POOL LIGHTS | | | SHOWN AS #14 AWG AND 20A OCP. PLEASE | | | CORRELATE. | | | | | | 4)NOTE: PLEASE CLARIFY OVEN SHOWN AS | | | ONLY 6KW. | | | | | | 5)NOTE: PLEASE NOTE THAT ON THE BOTTOM | | | OF LOAD CALCULATIONS, KW/.24V? | | | PLEASE CLARIFY MISPRINT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|