| Plan Review Notes For Permit 02051323 |
| Permit Number |
02051323 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-27 00:00:00 | PROVISO: | | | | | | AS PER 2001 FBC(M) 506.3.14.3 - EXHAUST | | | OUTLETS SHALL BE LOCATED NOT LESS THAN | | | 10 FT FROM PARTS OF THE SAME OR | | | CONTIGUOUS BUILDINGS, ADJACENT PROPERTY | | | LINES & AIR INTAKE OPENINGS. | | | | | | AS PER NFPA 96 4-8.2.1 (B) THE EXHAUST | | | FLOW DIRECTED UP & AWAY FROM THE SURFACE | | | OF THE ROOF & A MINIMUM OF 40" ABOVE THE | | | ROOF SURFACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|