Plan Review Notes
Plan Review Notes For Permit 02051323
Permit Number 02051323
Review Stop M
Sequence Number 2
Notes
Date Text
2002-06-27 00:00:00PROVISO:
  
 AS PER 2001 FBC(M) 506.3.14.3 - EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN
 10 FT FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES & AIR INTAKE OPENINGS.
  
 AS PER NFPA 96 4-8.2.1 (B) THE EXHAUST
 FLOW DIRECTED UP & AWAY FROM THE SURFACE
 OF THE ROOF & A MINIMUM OF 40" ABOVE THE
 ROOF SURFACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.