| Plan Review Notes For Permit 02051297 |
| Permit Number |
02051297 |
|
| Review Stop |
R |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-11-12 00:00:00 | REVISION DENIED | | | | | | 1) PROVIDE (2) COPIES OF THE SOIL TEST | | | REPORT. ONE COPY (SIGNED AND SEALED) | | | WILL BE KEPT FOR PUBLIC RECORD AND THE | | | OTHER WILL BE STAMPED AND RETURNED TO | | | HAVE AT THE JOB SITE. | | | | | | 2) INTERIOR BEARING WALL DETAIL ON A8 | | | REFRENCES SBCCI AND NOT 2001 FBC. DETAIL | | | SHOWS WOOD FLOOR TRUSSES AND NOT HAMBRO | | | JOISTS. PLEASE REVISE. | | | | | | 3) TYPICAL WALL SECTION ON A8 LISTS R-19 | | | ATTIC INSULATION AND THE ENERGY CALCS. | | | LIST R-30 INSULATION. PLEASE REVISE. | | | | | | 4) FIREBLOCKING IS REQUIRED AT STAIRS | | | PER FBC 2305.1.4 (3) OF MATERIALS | | | SPECIFIED IN FBC 2305.1.5. PLEASE | | | INDICATE LOCATIONS AND MATERIALS TO BE | | | USED ON THE PLANS. | | | | | | 5) THE FASTENERS USED TO SECURE HI-RIB | | | METAL LATHE ARE REQUIRED TO PROVIDE AT | | | LEAST 1-3/4" PENETRATION INTO HORIZONTAL | | | WOOD FRAMING MEMBERS PER FBC 2405.2.2 | | | AND ASTM C 1063. PLEASE REVISE BALCONY | | | SECTION ON A8 AND ENTRY SECTION ON A9. | | | | | | 6) WALL SECTION AT WALL SPANNING GARAGE | | | ON A9 SHOWS A STEEL I-BEAM SUPPORTING | | | THE WALL. THE OTHER SHEETS INDICATE | | | PRECAST LINTELS. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|