| 2002-10-02 00:00:00 | ************BUILDING PROVISO************ |
| | |
| | 1) PROVIDE A SOIL REPORT SIGNED AND |
| | SEALED BY A STATE OF FLORIDA SOIL |
| | ENGINEER INDICATING DEPTH THAT BOTTOM |
| | BEARING PILINGS ARE REQUIRED TO EXTEND |
| | TO ACHIEVE ADEQUATE BEARING. |
| | |
| | 2) PROVIDE A PILE LOCATION PLAN, WHICH |
| | SHOWS THE LOCATION AND DESIGNATION OF |
| | ALL PILES BY AN IDENTIFYING SYSTEM. ALL |
| | DETAILED RECORDS FOR INDIVIDUAL PILES |
| | SHALL BEAR AN IDENTIFICATION CORRESPOND- |
| | ING TO THAT ON THE PLAN. FBC SEC.1805.14 |
| | |
| | 3) THE QUALIFIED PILING INSPECTOR IS |
| | REQUIRED TO BE PRESENT WHEN THE PILES |
| | ARE BEING INSTALLED. HE SHALL SUBMIT |
| | DETAILED (SIGNED AND SEALED) REPORTS OF |
| | THE INSTALLATION OF EACH PILE, STATING |
| | THAT EACH IS CAPABLE OF SUPPORTING THE |
| | LOADS IMPOSED. |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - VINYL SOFFIT |
| | - DRAWING BO121 FOR OUTSWING FIBERGLASS |
| | DOOR |
| | - DRAWING D-408948 OR D-408958 FOR 16' |
| | WIDE GARAGE DOOR (EITHER OF THESE WILL |
| | MEET THE REQUIRED WINDLOAD PRESSURES) |
| | |
| | 5) STORM PANELS WILL REQUIRE A SEPARATE |
| | PERMIT WITH ADDITIONAL FEES. |