Plan Review Notes
Plan Review Notes For Permit 02051297
Permit Number 02051297
Review Stop R
Sequence Number 2
Notes
Date Text
2002-09-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE, AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 4) PLEASE SPECIFY A CALL SIZE FOR THE
 HORIZONTAL SLIDING WINDOW IN BEDROOM #3.
 SO THAT THE DIMENSIONS CAN BE DETERMINED
  
 5) INDICATE THE LOCATION OF THE CONTROL
 JOINTS FOR THE SLAB ON GROUND OR SPECIFY
 THE EXCEPTION THAT WILL BE USED. SEE
 FBC SEC.1909.3.
  
 6) ROOF SHEATHING DETAIL ON A-7 IS
 INCORRECT. PLEASE REVISE. SEE TABLE
 2306.1 OF CITY AMENDMENTS TO FBC.
  
 7) PROVIDE (2) COPIES OF HAMBRO
 INSTALLATION MANUAL.
  
 8) THE INTERIOR BEARING WALL DETAIL ON
 A-8 DOES NOT SHOW HAMBRO JOISTS BEARING
 ON IT. PLEASE REVISE.
  
 9) HIGH RIB METAL LATH REQUIRES NAILS OR
 STAPLES THAT PROVIDE AT LEAST 1-3/4"
 PENETRATION INTO HORIZONTAL WOOD
 FRAMING MEMBERS SPACED NOT MORE THAN 7"
 ON CENTER ALONG SUPPORTS, PER ASTM C
 1063. PLEASE REVISE THE BALCONY SECTION
 ON A-8 AND THE ENTRY SECTION ON A-9.
  
 10) PROVIDE FIRE BLOCKING AT THE TOP AND
 BOTTOM OF THE STAIR RUN AS REQUIRED BY
 FBC SEC. 2305.1.4.
  
 11)PROVIDE A SOIL INVESTIGATION AND TEST
 REPORT. GEOTECHNICAL REPORT AND
 RECOMMENDATIONS SIGNED AND SEALED BY A
 STATE OF FLORIDA LICENSED SOIL ENGINEER
 IS REQUIRED. CITY OF WPB AMENDMENTS TO
 THE FBC SEC. 1804.2.2. AND FBC 1805.1
  
 12) PROVIDE A PILE LOCATION PLAN, WHICH
 SHOWS THE LOCATION AND DESIGNATION OF
 ALL PILES BY AN IDENTIFYING SYSTEM. ALL
 DETAILED RECORDS FOR INDIVIDUAL PILES
 SHALL BEAR AN IDENTIFICATION CORRESPOND-
 ING TO THAT ON PLAN. FBC SEC.1805.14
  
 13) PROVIDE THE NAME OF THE QUALIFIED
 INSPECTOR,THAT WILL BE PRESENT WHEN THE
 THE PILES ARE BEING INSTALLED, FOR
 APPROVAL OF THE BUILDING OFFICIAL PER
 FBC 1805.12. THE INSPECTOR SHALL SUBMIT
 DETAILED (SIGNED AND SEALED) REPORTS OF
 THE INSTALLATION OF EACH PILE, STATING
 THAT EACH IS CAPABLE OF SUPPORTING THE
 REQUIRED LOADS.
  
 15) CITY OF WPB AMENDMENTS SEC.1804.1.7
 REQUIRES THE FLOOR ELEVATION AT THE
 PERIMETER OF MONOLITHIC FOUNDATIONS AT
 HABITABLE AREAS TO BE A MINIMUM OF 4"
 ABOVE FINISH GRADE. PLEASE INDICATE ON
 THE PLANS.
  
 16) PLEASE SPECIFY THE EMBEDMENT DEPTH
 OF THE #5 VERTICAL RODS INTO THE GRADE
 BEAMS ON SECTION ON A-9.
  
 17) THE WALL SECTION FOR THE WALL ABOVE
 THE GARAGE ON A-9, SHOWS A STEEL I-BEAM
 SUPPORTING THE JOISTS AND WALL. SHEET
 A-4.1 SHOWS LINTEL BEAMS. PLEASE CLARIFY
 AND CORRECT.
  
 18) SPECIFY THE LOCATION AND MATERIAL
 THAT WILL BE USED FOR THE DRAFTSTOPS IN
 THE FLOOR/CEILING ASSEMBLY REQUIRED BY
 FBC SEC.2305.2.2 (SEE FBC 2306.2.6)
  
 19) SPECIFY THE HURRICANE CLIP TO BE
 USED AT THE TYPICAL GABLE OVERHANG
 DETAIL ON SHEET A-6.
  
 20) PLEASE UPDATE THE REFERENCE TO THE
 SBCCI AT THE INTERIOR BEARING WALL ON
 A-8 TO REFERENCE THE 2001 FBC.
  
 21) INDICATE ON THE PLANS THE REQUIRED
 NET FREE VENTILATING AREA FOR THE ATTIC
 SPACE AND SHOW THAT THE VINYL SOFFIT
 WILL PROVIDE THE REQUIRED NET FREE AREA.
 PROVIDE CALCULATIONS. FBC SEC.2309.7
  
 22) PROVIDE PRODUCT APPROVAL FOR THE
 VINYL SOFFIT WITH INFORMATION FOR
 WINDLOADING AS REQUIRED FOR COMPONENTS
 AND CLADDING.
  
 23) INDICATE ON PLANS THAT WINDOWS
 WITHIN 36" HORIZONTALLY OF A SHOWER OR
 TUB IS REQUIRED TO HAVE SAFETY GLAZING
 IF WITHIN 60" OF THE STANDING OR
 WALKING SURFACE PER FBC 2405.2.1(2).
 SEE CABANA BATH AND BATH #2.
  
 24) NOTE 7 UNDER GENERAL NOTES ON A-1
 SPECIFIES PGT IMPACT RESISTANT WINDOWS.
 THE PRODUCT APPROVALS SUBMITTED ARE FOR
 NORANDEX NON IMPACT WINDOWS. PLEASE
 CLARIFY AND CORRECT.
  
 25) THE GARAGE COLUMN DETAIL ON A-9 DOES
 NOT SHOW A BUCK OR BUCK ATTACHMENT
 DETAILS. THE GARAGE DOOR PRODUCT
 APPROVAL REQUIRES A WOOD BUCK. PLEASE
 PROVIDE A BUCK DETAIL THAT COORDINATES
 WITH THE PRODUCT APPROVAL AND NOTE 20 ON
 SHEET A-1.
  
 26) THE SITE SPECIFIC PRODUCT APPROVAL
 FOR THE NORANDEX PRODUCTS REQUIRES THE
 ORIGINAL SIGNATURE, DATE AND EMBOSSED
 SEAL OF THE ENGINEER CERTIFYING THE
 PRODUCT AND OF THE DESIGNER OF RECORD
 FOR THE STRUCTURE.
  
 27) THE SIDE SWING DOOR AT THE GARAGE IS
 INDICATED AS A METAL DOOR ON THE PLANS.
 THERE WERE NO PRODUCT APPROVALS FOR
 METAL DOORS SUBMITTED. PROVIDE PROD.
 APPR. FOR MTAL DOOR OR REVISE PLAN.
  
 28) ONE SHEET (#1 OF 3) OF DRAWING BO121
 IS MISSING FROM THE OUTSWING FIBERGLASS
 DOOR PRODUCT APPROVAL.
  
 29) THE DESIGN WINDLOAD OF THE NORANDEX
 HORIZONTAL SLIDING WINDOWS (+/- 45PSF)
 DO NOT MEET THE NEGATIVE WINDLOAD
 PRESSURE REQUIRED BY THE STRUCTURE
 (-46.2 PSF).
  
 30) THE DESIGN WINDLOAD PRESSURES OF THE
 NORANDEX SINGLE HUNG WINDOWS +/- 45PSF
 DOES NOT MEET THE NEGATIVE WINDLOAD
 PRESSURE INDICATED FOR THE STRUCTURE.
  
 31) THE ROLL SHUTTER HAS A DESIGN
 PRESSURE OF +/- 44 PSF FOR A 192" WIDTH
 AND THE OPENING HAS A HIGHER NEGATIVE
 PRESSURE (-46.2PSF) PER THE PLANS.
 PROVIDE THE ELECTRICAL REQUIREMENTS,
 MOTOR SPECIFICATIONS, LISTING INFO.,ETC.
  
 32) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. CIRCLE OR
 HIGHLIGHT THE INSTALLATION AND FASTENER
 TYPES THAT WILL BE USED ON THE PRODUCT
 APPROVAL. INDICATE WHICH TYPE OF PANEL
 OR PANELS BEING USED AND MAKE SURE THE
 APPROPRIATE DRAWINGS ARE SUBMITTED.
 (WHAT PROD.APPROV. DOES THE 02-055
 DRAWINGS CORRESPOND TO?)
 THIS INFORMATION IS REQUIRED AT THE
 TIME THE PERMIT FOR THE STRUCTURE IS
 ISSUED OR A SEPARATE STORM PANEL PERMIT
 WITH ADDITIONAL FEES WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202