| Plan Review Notes For Permit 02051297 |
| Permit Number |
02051297 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-28 00:00:00 | UNSAT | | | ~~~~~ | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} INDICATE CONDUIT & WIRE SIZE AND | | | TYPE FOR THE RISER. | | | | | | 3} INDICATE PANEL LOCATIONS ON PLAN. | | | | | | 4} INDICATE HOW THE 100 AMP "SUB-PANEL" | | | IS BEING FED,ALSO CONDUIT AND WIRE SIZE. | | | | | | 5} PLEASE PROVIDE PANEL SCHEDULES. | | | | | | 6} INCLUDE THE LAUNDRY CIRCUIT IN THE | | | LOAD CALC PER 210-16(B). | | | | | | 7} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 8} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 9} PLEASE NOTE THE "HEAT STRIPS" LISTED | | | ON THE LOAD CALCULATIONS MUST COMPLY | | | WITH 424-3(B),OCP & CONDUCTORS @ 125%. | | | | | | 10} 1ST FLOOR STAIRWELL,SMOKE DETECTOR | | | TO COMPLY WITH 2-5.2.1.2. | | | | | | 11} SMOKE DETECTOR IN THE MASTER BEDROOM | | | TO COMPLY WITH 2-2.1.1.1. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|