Plan Review Notes
Plan Review Notes For Permit 02051297
Permit Number 02051297
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-28 00:00:00UNSAT
 ~~~~~
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE CONDUIT & WIRE SIZE AND
 TYPE FOR THE RISER.
  
 3} INDICATE PANEL LOCATIONS ON PLAN.
  
 4} INDICATE HOW THE 100 AMP "SUB-PANEL"
 IS BEING FED,ALSO CONDUIT AND WIRE SIZE.
  
 5} PLEASE PROVIDE PANEL SCHEDULES.
  
 6} INCLUDE THE LAUNDRY CIRCUIT IN THE
 LOAD CALC PER 210-16(B).
  
 7} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 8} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 9} PLEASE NOTE THE "HEAT STRIPS" LISTED
 ON THE LOAD CALCULATIONS MUST COMPLY
 WITH 424-3(B),OCP & CONDUCTORS @ 125%.
  
 10} 1ST FLOOR STAIRWELL,SMOKE DETECTOR
 TO COMPLY WITH 2-5.2.1.2.
  
 11} SMOKE DETECTOR IN THE MASTER BEDROOM
 TO COMPLY WITH 2-2.1.1.1.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392